ELE11-01976
| ELE-Aging Inspection | 11/5/2014 | 11/5/2014 | 11/7/2014 11:45:01 AM | | DONE |
|
|
left another message for Terry
|
ELE11-01876
| ELE-Aging Inspection | 11/5/2014 | 11/5/2014 | 11/7/2014 11:41:11 AM | | DONE |
|
|
did drive by final ok
|
ELE14-03096
| Temporary Service | 11/5/2014 | 11/5/2014 | 11/6/2014 8:11:39 AM | P | PASS |
|
|
any questions please let me know, thx, TW. Phone #: ###-#### Inspection requested via web by Stephen Kren t/s u/g n ok
|
GCE14-00166
| GCE-Final | 11/5/2014 | 11/5/2014 | 11/5/2014 3:38:25 PM | P | FAIL |
|
|
Cal ###-#### update panel schedules, 210.8(B)(7)-GFCI protection required within 6 foot of sink. 210.62-show windows need receptacle every 12 foot. 220.14-show windows require 200 va per foot
|
ELE14-03072
| Permanent Service | 11/5/2014 | 11/5/2014 | 11/5/2014 1:24:00 PM | P | PASS |
|
|
Rocky Phone #: ###-#### p/s o/h rec ok
|
ELE14-03085
| Conference | 11/4/2014 | 11/5/2014 | 11/5/2014 10:50:48 AM | A | DONE |
|
|
Geoff Hannaford is contact - ###-####. thank you Phone #: ###-#### Inspection requested via web by Debby Pierce discuss junction box access in new hard lid ceiling
|
ELE14-02429
| Final | 10/29/2014 | 11/5/2014 | 11/5/2014 10:14:25 AM | A | PASS |
|
|
final on lighting retrofit Phone #: ###-#### Inspection requested via web by Tim Dunlop final ok
|
ELE14-02925
| Final | 11/4/2014 | 11/5/2014 | 11/5/2014 9:55:10 AM | A | PASS |
|
|
Gate open, Phone #: ###-#### Inspection requested via web by Jesse Fuentes final ok heat pump hooked up. Jesse says he never touched it.
|
ELE14-03052
| Rough-In Permanent Service | 11/5/2014 | 11/5/2014 | 11/5/2014 9:37:33 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Greg Idsinga r/i ok p/s o/h n ok
|
ELE14-02130
| Final | 11/4/2014 | 11/5/2014 | 11/5/2014 8:50:00 AM | A | PASS |
|
|
I will be onsite to get inspector in from 8:30 till 10:00 am. This is a secure building call and I will meet you at front door. Thanks
Mike Cole B ; B ###-#### Phone #: ###-#### Inspection requested via web by Mike Cole Unit 405 final ok
|
ELE14-02478
| Electrical Rough-In | 11/4/2014 | 11/5/2014 | 11/5/2014 8:24:34 AM | A | PASS |
|
|
Partial Electrical Rough in Roof Phone #: ###-#### Inspection requested via web by jason williams r/i ok parapet roof walls
|