Inspections for the day of: Wednesday, November 5, 2014.
Number of inspections: 19
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorCevyn Recla
TitleELE-INSPECTOR
Phone #985-3493
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE12-01598 ELE-Aging Inspection11/5/201411/5/201411/7/2014 9:16:48 AM DONE
Left message with contractor
ELE14-02270 Final11/4/201411/5/201411/5/2014 5:03:00 PMPFAIL
36 solar panels.
AC micro-inverter system. No DC voltage.
We used Enphase M250 micro inverters and ET Solar solar panels, both listed and approved.
This is a pole mount system, mounted back behind the house.
There is a single home run, in conduit, running 300 feet from the solar array to the knife switch, located next to meter base on south corner of home. From the knife switch to the 40 amp breaker in main panel, at the top, opposite the feeder lugs. The solar breaker is clearly marked with label plate, and its circuit number identified in the knife switch and the panel schedule.
The inverters, panels and rails are all bonded with a number 6 ground that is bonded to one of the 6" poles that runs 8 feet deep into the ground. The equipment/circuit ground is a number 6 in the conduit that runs back to the service ground.

For access to the garage/main panel, call home owner at 208.867.8002. His name is Dwayne Peters.

Thanks guys
Phone #: ###-#### Inspection requested via web by Ryan King
No underground inspection performed
352.30 Securing and support of riser
250.92B.4 bond bushings at concentric knockouts
250.96 non conductive paint to be removed at ground point
240.15B circuit breakers shall open all ungrounded conductors simultaneously
no supplemental ground
Spoke to Jason Blais, 11-5-14, 2:30 PM, no building permit required
ELE14-01597 Electrical Rough-In11/5/201411/5/201411/5/2014 4:24:51 PMPCANC
final on several office areas ready to occupy , also rough-in to cover ceilings Shane is the contact on site ###-#### Phone #: ###-#### Inspection requested via web by Shawna Gates
Contractor put inspection for wrong date.
ELE14-03099 Permanent Service11/5/201411/5/201411/5/2014 4:12:03 PMPPASS
PS, OH, RC, OK
ELE14-03099 Final11/5/201411/5/201411/5/2014 4:11:31 PMPFAIL
Larry Phone #: ###-####
Spoke to contractor, no access, need to see grounding system
110.22 Each disconecting means shall be identified for its purpose
250.54 D 2 Supplemental elctrode required
312.5 B NM cable shall be bushed at openings

City code 4.5.32 Known code violations shall not be retained
ELE14-02512 Final11/5/201411/5/201411/5/2014 3:27:29 PMPFAIL
Phone #: ###-#### Inspection requested via web by steve sellers
225.32 Disconnecting means shall be located at nearest point of entrance to seperate structure
110.26A Working clearance in front of panel
ELE14-03004 Final11/4/201411/5/201411/5/2014 1:27:44 PMPCANC
jASON gAYTHWAITE IS OUR JOURNEYMAN CONTACT Phone #: ###-#### Inspection requested via web by Kelly Felin
cancelled by contractor, conducted conference
ELE14-03004 Conference11/5/201411/5/201411/5/2014 1:27:09 PMPDONE
jASON gAYTHWAITE IS OUR JOURNEYMAN CONTACT Phone #: ###-#### Inspection requested via web by Kelly Felin
Discuss requirements for service change
ELE14-01682 Final11/4/201411/5/201411/5/2014 12:56:11 PMPPART
Phone #: ###-#### Inspection requested via web by Spencer McLean
Temp occ OK, need to see HVAC systems, no access to rooftop, unsafe, and discuss water line with Daryl
ELE14-03004 Final11/4/201411/5/201411/5/2014 11:17:14 AMPCANC
jASON gAYTHWAITE IS OUR JOURNEYMAN CONTACT Phone #: ###-#### Inspection requested via web by Kelly Felin
Posted two final inspections, cancelled one, Cevyn
ELE14-02730 Final11/4/201411/5/201411/5/2014 11:13:23 AMAPASS
Phone #: ###-#### Inspection requested via web by Greg Traudt

FInal OK
ELE14-03080 Electrical Rough-In11/4/201411/5/201411/5/2014 10:42:23 AMANR
THIS IS FOR UNDERGROUND POWER INSPECTION ONLY. Underground inspection is not an option so I did rough in inspection.
Trench is in residential backyard which requires
18" minimum, did not know if you needed to see it or not ###-####. AM or PM will work. Phone #: ###-#### Inspection requested via web by Cindie Swaim
Not REady, conduit not installed in trench yet
ELE14-00437 Final11/4/201411/5/201411/5/2014 10:25:02 AMAPASS
FInal OK
ELE14-03097 Electrical Rough-In11/5/201411/5/201411/5/2014 10:12:33 AMAPASS
Unit should be open all day. Thanks Shaun ###-#### Phone #: ###-#### Inspection requested via web by Shaun Kirkman
RI ok to cover. For final inspection, I will need to see permanent labeling for meter base, and panel along with panel schedule
ELE14-01682 Rough-In Permanent Service11/4/201411/5/201411/5/2014 9:59:13 AMAPASS
Please inspect the Service as we will have IPCO shut down the service in the AM for your inspection. Phone #: ###-#### Inspection requested via web by Spencer McLean
PS, UG, N OK
ELE14-02007 Rough-In Permanent Service11/5/201411/5/201411/5/2014 9:10:27 AMAPASS
rough in ok to cover
PS,UG,N,OK
ELE14-02007 Final11/4/201411/5/201411/5/2014 7:05:52 AMACANC
Phone #: ###-####
Wrong inspection entered by office, CR
ELE14-02270 Rough-In Permanent Service11/5/201411/5/201411/5/2014 7:04:25 AMACANC
wrong insp.
ELE14-00437 Final11/3/201411/5/201411/4/2014 9:14:34 AMANR
Erin Phone #: ###-####
left message with owner, not ready