FIR14-00344
| INSP-Sprinkler Rough-in | 11/5/2014 | 11/5/2014 | 11/6/2014 7:27:03 AM | P | PART |
|
|
|
FIR14-00500
| INSP-Sprinkler Rough-in | 11/5/2014 | 11/5/2014 | 11/5/2014 3:53:18 PM | P | FAIL |
|
|
Noted several locations missing hanger restraint at pendent heads. Remove non-related trade work supported by fire protection piping.
|
BLD14-02181
| FIRE-Conference | 11/5/2014 | 11/5/2014 | 11/5/2014 3:48:53 PM | P | DONE |
|
|
Regarding fire extinguisher placement, fire life safety inspection items.
|
FIR14-00612
| INSP-Sprinkler Rough-in | 11/4/2014 | 11/5/2014 | 11/5/2014 11:53:49 AM | A | PART |
|
|
Completed inspection for the new dry system mains and branchlines including the exterior soffits and attic spaces. Need to provide coverage below the elevated catwalk or meet exceptions allowed per NFPA. Remainder of coverage okayed, DP are not yet installed.
|
BLD14-00947
| FIRE-Final Inspection | 11/4/2014 | 11/5/2014 | 11/5/2014 11:49:32 AM | A | PASS |
|
|
Fire life safety inspection completed acceptable.
|