Inspections for the day of: Thursday, November 5, 2015.
Number of inspections: 11
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorBill VanDegrift
TitlePLM-INSPECTOR
Phone #794-9372
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
MEC15-05237 Final11/5/201511/5/201511/5/2015 5:14:31 PMPPART
Francis will call insp when it''s close to finish, so you can witness pressure test on flue Phone #: ###-#### Inspection requested via web by Floyd Floyd Peek needs combustion air glued.
MEC15-05223 Final11/4/201511/5/201511/5/2015 2:17:25 PMPPASS
installer Brandan ###-#### Phone #: ###-#### Inspection requested via web by Dustin Rich
MEC15-04218 Final11/5/201511/5/201511/5/2015 2:03:12 PMPNR
Bj 5730755 Inspection requested via web by william kerwin no air balance report
MEC15-05038 Rough-in11/5/201511/5/201511/5/2015 2:01:21 PMPPASS
Bj 5730755 Inspection requested via web by william kerwin ri 20# gas and 5# flue ok
MEC15-05211 Final11/5/201511/5/201511/5/2015 1:21:15 PMPPASS
Home Owner Terry ###-#### - Please contact Patrick ###-#### to insure required changes have been completed. Thank you! Phone #: ###-#### Inspection requested via web by SOPHIA FLEMING
MEC15-04713 Rough-in11/4/201511/5/201511/5/2015 11:28:43 AMAFAIL
Phone #: ###-#### Inspection requested via web by Krista Boss
1) gas test failed
2) flue test failed
3) remove concentric reducer from horizontal flue
4) missing supply in master (170cfm)
5) nail plate at dryer exhaust on 1st floor 6) need combustion air for the water heater from someplace other than the mechanically vented crawlspace.
MEC15-05224 Final11/4/201511/5/201511/5/2015 11:14:46 AMAPASS
Pressure Test Phone #: ###-#### Inspection requested via web by jeff jedlick 20# test ok
MEC15-05222 Pressure Test11/4/201511/5/201511/5/2015 11:14:10 AMAPASS
Adam: ###-####
Shaun: ###-#### Phone #: ###-#### Inspection requested via web by Frank Marturello 20# test ok
MEC15-05224 Final11/5/201511/5/201511/5/2015 11:13:30 AMPPASS
Adam: ###-####
Shaun: ###-#### Phone #: ###-#### Inspection requested via web by Frank Marturello 20# test ok final ok
MEC15-05222 Rough-in11/4/201511/5/201511/5/2015 10:35:50 AMAPASS
Adam: ###-####
Shaun: ###-#### Phone #: ###-#### Inspection requested via web by Frank Marturello ri 20# gas and 5# flue ok
MEC15-04560 Final11/4/201511/5/201511/5/2015 8:57:03 AMANR
Phone #: ###-#### Inspection requested via web by Karl Hestekin
1) needs an economizer on the new rtu.
2) need to verify the duct detectors on all the rtu's over 2000 cfm
3) need exhaust in the mens shower room.