ELE15-03401
| Final | 11/4/2015 | 11/5/2015 | 11/5/2015 2:55:53 PM | P | PASS |
|
|
Thanks Phone #: ###-#### Inspection requested via web by Scott Campbell final ok
|
ELE15-03322
| Rough-In Permanent Service | 11/5/2015 | 11/5/2015 | 11/5/2015 2:32:12 PM | P | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Eric Brown whole house remodel rough-in ok cover t/s o/h n ok
|
ELE15-03584
| Temporary Service | 11/4/2015 | 11/5/2015 | 11/5/2015 2:24:40 PM | P | PASS |
|
|
We are requesting a temp power inspection for tomorrow 11-5-16 in the afternoon. Our contact is Trent @ ###-####. Thank you, Phone #: ###-#### Inspection requested via web by Clint Tate t/s o/h n ok
|
ELE15-03573
| Final | 11/4/2015 | 11/5/2015 | 11/5/2015 1:37:27 PM | P | FAIL |
|
|
If possible; late afternoon inspection. Thank you Phone #: ###-#### Inspection requested via web by Lonnie Sorichta 210.52 branch circuit added in bathroom shall be 20amp dedicated 210.12 branch circuit added in bedroom for computer shall be be AFCI protected
|
ELE99-01763
| Final | 11/4/2015 | 11/5/2015 | 11/5/2015 1:12:01 PM | P | PASS |
|
|
Tony-pleae call 1 hr prior to meet Phone #: ###-#### final ok
|
ELE15-03244
| Final | 11/5/2015 | 11/5/2015 | 11/5/2015 1:02:29 PM | P | CANC |
|
|
We need final for a hot tub connection. Thank you Phone #: ###-#### Inspection requested via web by Thomas Jenkins
|
ELE15-03586
| Electrical Rough-In | 11/5/2015 | 11/5/2015 | 11/5/2015 12:33:09 PM | P | CANC |
|
|
as close to noon as you can please Phone #: ###-#### Inspection requested via web by Andy Derrick needed conference
|
ELE15-03586
| Conference | 11/5/2015 | 11/5/2015 | 11/5/2015 12:33:00 PM | P | DONE |
|
|
as close to noon as you can please Phone #: ###-#### Inspection requested via web by Andy Derrick discussed mounting hot tub disc on back side due to no where else to locate it for code requirements
|
ELE15-03536
| Rough-In Permanent Service | 11/5/2015 | 11/5/2015 | 11/5/2015 10:43:00 AM | P | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Darryn Coburn roigh-in ok cover p/s u/g n ok
|
ELE15-03537
| Rough-In Permanent Service | 11/5/2015 | 11/5/2015 | 11/5/2015 10:41:43 AM | P | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Darryn Coburn rough-in ok cover p/s u/g n ok
|
ELE15-03209
| Electrical Rough-In | 11/4/2015 | 11/5/2015 | 11/5/2015 10:04:33 AM | A | PASS |
|
|
Remodel the upstairs. Access and stairs in the back. Phone #: ###-#### Inspection requested via web by Greg Idsinga upstairs bed bath and office rough-in ok cover
|
ELE15-03495
| Final | 11/4/2015 | 11/5/2015 | 11/5/2015 9:43:56 AM | A | CANC |
|
|
Phone #: ###-#### Inspection requested via web by Randy Fletcher needed rough-in
|
ELE15-03495
| Electrical Rough-In | 11/5/2015 | 11/5/2015 | 11/5/2015 9:43:40 AM | P | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Randy Fletcher back rooms and circuits feeding rough-in ok cover
|
ELE15-03581
| Electrical Rough-In | 11/4/2015 | 11/5/2015 | 11/5/2015 9:19:12 AM | A | NR |
|
|
Phone #: ###-#### Inspection requested via web by Dan Rohl not ready boxes not set wires hanging out of walls and cieling
|
ELE15-03017
| Electrical Rough-In | 11/4/2015 | 11/5/2015 | 11/5/2015 9:08:37 AM | A | PASS |
|
|
Lock box 4545. Please call Calvin with any questions ###-####. Thanks Phone #: ###-#### Inspection requested via web by Clay Morgan kitchen and back bath downstairs hallway rough-in ok cover
|
ELE15-03017
| Electrical Rough-In | 11/4/2015 | 11/5/2015 | 11/5/2015 9:07:51 AM | A | PASS |
|
|
Lock box 4545. Please call Calvin with any questions ###-####. Thanks Phone #: ###-#### Inspection requested via web by Clay Morgan kitchen back bath and downstairs hall way rough-in ok cover
|