BLD05-01282
| FIRE-Conference | 10/28/2015 | 11/4/2015 | | A | |
|
|
follow up
|
BLD15-00128
| FIRE-Final Inspection | 11/4/2015 | 11/5/2015 | 11/5/2015 2:47:26 PM | P | FAIL |
|
|
Provide fire dept review comments, provide the additioanl four fire extinguishers, provide the two additional exit discharge lights and repair the two non-functional emergency lights, replace the bent sprinkler hanger rod and provide cages for the upright heads underneath the stairs. Provide fire dept access around the north side of the building per the approved plans.
|
FIR15-00573
| INSP-Final Inspection | 10/30/2015 | 11/5/2015 | 11/5/2015 1:49:01 PM | P | CANC |
|
|