MEC18-01885
| Final | 11/5/2018 | 11/5/2018 | 11/5/2018 3:43:51 PM | P | NH |
|
|
LATE PM, IF POSSIBLE, ROB ###-#### Phone #: ###-#### Inspection requested via web by Arielle Hendricks- no access
|
MEC18-04924
| Rough-in | 11/5/2018 | 11/5/2018 | 11/5/2018 3:08:45 PM | P | FAIL |
|
|
Phone #: ###-#### Inspection requested via web by Lynn Johnston - Man J needs tto be approved by the city and stamped - crawl is not finished - side wall supply run in bathroom upstairs needs to be ducted out of cabinet area and looks to be blocked by water lines coming through floor
|
MEC18-04924
| Pressure Test | 11/5/2018 | 11/5/2018 | 11/5/2018 3:05:55 PM | P | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Lynn Johnston- 20lb gas pressure test ok- 5lb flue pressure test ok
|
MEC18-05249
| Final | 11/1/2018 | 11/5/2018 | 11/5/2018 2:11:16 PM | P | PASS |
|
|
field super: Chad Robertston Phone #: ###-#### Inspection requested via web by Lisa Whitney - furnace only ok
|
MEC18-05294
| Pressure Test | 11/5/2018 | 11/5/2018 | 11/5/2018 1:46:22 PM | P | PASS |
|
|
Call Greg if you have any questions ###-#### Phone #: ###-#### Inspection requested via web by Greg Mendiola - underground 20lb gas pressure test ok- underground 60lb gas pressure test ok
|
MEC18-04516
| Rough-in | 11/2/2018 | 11/5/2018 | 11/5/2018 1:32:51 PM | P | PASS |
|
|
Mechanical Rough-in Inspection. Aaron Roberts is the Site Contact: ###-####. Phone #: ###-#### Inspection requested via web by RM Mechanical- R/I ok - cover ok
|
MEC18-03855
| Final | 11/2/2018 | 11/5/2018 | 11/5/2018 10:36:50 AM | A | FAIL |
|
|
Phone #: ###-#### Inspection requested via web by Dawn Kalsbeek- both furnaces need a wet switch installed on the secondary drain
|
MEC18-03984
| Final | 11/2/2018 | 11/5/2018 | 11/5/2018 10:17:40 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Dawn Kalsbeek- final ok
|
MEC18-04116
| Rough-in | 11/2/2018 | 11/5/2018 | 11/5/2018 10:02:53 AM | A | PASS |
|
|
Raised unit Phone #: ###-#### Inspection requested via web by Dan Otero- outdoor fireplace R/I ok
|
MEC18-05291
| Pressure Test | 11/2/2018 | 11/5/2018 | 11/5/2018 9:48:44 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Dawn Kalsbeek- 20lb gas pressure test ok
|
MEC18-05291
| Rough-in | 11/2/2018 | 11/5/2018 | 11/5/2018 9:48:12 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Dawn Kalsbeek- R/I ok
|
MEC18-04657
| Pressure Test | 11/4/2018 | 11/5/2018 | 11/5/2018 9:24:56 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Michelle Lythgoe- 20lb gas pressure test ok- checked sizing of new gas lines to bbq,range, and dryer and all looks good
|