Inspections for the day of: Monday, November 5, 2018.
Number of inspections: 12
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJack Reynolds
TitleMEC INSPECTOR
Phone #208-803-2395
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
MEC18-01885 Final11/5/201811/5/201811/5/2018 3:43:51 PMPNH
LATE PM, IF POSSIBLE, ROB ###-#### Phone #: ###-#### Inspection requested via web by Arielle Hendricks- no access
MEC18-04924 Rough-in11/5/201811/5/201811/5/2018 3:08:45 PMPFAIL
Phone #: ###-#### Inspection requested via web by Lynn Johnston
- Man J needs tto be approved by the city and stamped
- crawl is not finished
- side wall supply run in bathroom upstairs needs to be ducted out of cabinet area and looks to be blocked by water lines coming through floor
MEC18-04924 Pressure Test11/5/201811/5/201811/5/2018 3:05:55 PMPPASS
Phone #: ###-#### Inspection requested via web by Lynn Johnston- 20lb gas pressure test ok- 5lb flue pressure test ok
MEC18-05249 Final11/1/201811/5/201811/5/2018 2:11:16 PMPPASS
field super: Chad Robertston Phone #: ###-#### Inspection requested via web by Lisa Whitney
- furnace only ok
MEC18-05294 Pressure Test11/5/201811/5/201811/5/2018 1:46:22 PMPPASS
Call Greg if you have any questions ###-#### Phone #: ###-#### Inspection requested via web by Greg Mendiola
- underground 20lb gas pressure test ok- underground 60lb gas pressure test ok
MEC18-04516 Rough-in11/2/201811/5/201811/5/2018 1:32:51 PMPPASS
Mechanical Rough-in Inspection. Aaron Roberts is the Site Contact: ###-####. Phone #: ###-#### Inspection requested via web by RM Mechanical- R/I ok - cover ok
MEC18-03855 Final11/2/201811/5/201811/5/2018 10:36:50 AMAFAIL
Phone #: ###-#### Inspection requested via web by Dawn Kalsbeek- both furnaces need a wet switch installed on the secondary drain
MEC18-03984 Final11/2/201811/5/201811/5/2018 10:17:40 AMAPASS
Phone #: ###-#### Inspection requested via web by Dawn Kalsbeek- final ok
MEC18-04116 Rough-in11/2/201811/5/201811/5/2018 10:02:53 AMAPASS
Raised unit Phone #: ###-#### Inspection requested via web by Dan Otero- outdoor fireplace R/I ok
MEC18-05291 Pressure Test11/2/201811/5/201811/5/2018 9:48:44 AMAPASS
Phone #: ###-#### Inspection requested via web by Dawn Kalsbeek- 20lb gas pressure test ok
MEC18-05291 Rough-in11/2/201811/5/201811/5/2018 9:48:12 AMAPASS
Phone #: ###-#### Inspection requested via web by Dawn Kalsbeek- R/I ok
MEC18-04657 Pressure Test11/4/201811/5/201811/5/2018 9:24:56 AMAPASS
Phone #: ###-#### Inspection requested via web by Michelle Lythgoe- 20lb gas pressure test ok- checked sizing of new gas lines to bbq,range, and dryer and all looks good