Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
MEC19-00431 Conference11/5/201911/5/201911/5/2019 3:41:01 PMPDONE
2:30 - Went by with the other trade inspector/supervisors and met with the homeowner. I gave her a correction notice stating the following.
1. Need to remove the supply grills from the floor of the shower and relocte a minimum of 6 feet above the floor.
2. Need to remove return grill from shower room.
3. Need to remove ducted return grill from bedroom with toilet open to to the room. (transfer grill okay).
4. Need to submit a new manual J showing the changes.
5. Need to submit new architectural drawings to plan review for approval.
MEC19-03746 Final11/5/201911/5/201911/5/2019 12:52:16 PMAPASS