FIR01-00567
| INSP-Sprinkler Rough-in | 11/5/2001 | 11/6/2001 | 11/6/2001 12:00:00 AM | A | PART |
|
|
Restroom area ok to cover 11/6/2001 10:57:40 AM
|
FIR01-00343
| INSP-Final Inspection | 11/5/2001 | 11/6/2001 | 11/6/2001 12:00:00 AM | A | PASS |
|
|
Fire sprinkler system finaled. OK for perm occ. 11/8/2001 11:43:45 AM
|
FIR01-00386
| INSP-Sprinkler Rough-in | 11/6/2001 | 11/6/2001 | 11/6/2001 12:00:00 AM | A | PART |
|
|
Added by Inspector: 430 On 11/6/2001 9:48:22 AM East office area OK for cover.
|
FIR01-00405
| INSP-Final Inspection | 11/6/2001 | 11/6/2001 | 11/6/2001 12:00:00 AM | A | PASS |
|
|
Added by Inspector: 430 On 11/6/2001 10:28:23 AM OK for perm occ
|
BLD01-02767
| FIRE-Alarm Testing | 11/5/2001 | 11/6/2001 | 11/6/2001 12:00:00 AM | A | PASS |
|
|
###-#### CAMI OK for perm occ 11/6/2001 10:14:34 AM
|
BLD01-00290
| FIRE-Final Inspection | 11/5/2001 | 11/6/2001 | 11/6/2001 12:00:00 AM | A | NR |
|
|
Had conference with superintendant on requirements for the life/safety inspection 11/6/2001 11:21:51 AM
|
BLD00-01531
| FIRE-Supply Line Hydro | 11/5/2001 | 11/6/2001 | 11/6/2001 12:00:00 AM | P | FAIL |
|
|
3rd floor a/v's wrong candella, batteries in facp wrong, plans need resubmitted with additional detectors shown, provide map at facp, post sign on riser door, provide phone jacks, provide proper recall, provide address for remote station 11/7/2001 9:50:29 AM
|
BLD01-02625
| FIRE-Final Inspection | 11/6/2001 | 11/6/2001 | 11/6/2001 12:00:00 AM | P | PART |
|
|
Provide a audio/visual alarm device in a normally occupied area. Verify smoke detector near the fire alarm panel is a system detector. If not add detector. 11/8/2001 11:42:44 AM
|