Inspections for the day of: Tuesday, November 6, 2001.
Number of inspections: 8
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR01-00567 INSP-Sprinkler Rough-in11/5/200111/6/200111/6/2001 12:00:00 AMAPART
Restroom area ok to cover 11/6/2001 10:57:40 AM
FIR01-00343 INSP-Final Inspection11/5/200111/6/200111/6/2001 12:00:00 AMAPASS
Fire sprinkler system finaled. OK for perm occ. 11/8/2001 11:43:45 AM
FIR01-00386 INSP-Sprinkler Rough-in11/6/200111/6/200111/6/2001 12:00:00 AMAPART
Added by Inspector: 430 On 11/6/2001 9:48:22 AM East office area OK for cover.
FIR01-00405 INSP-Final Inspection11/6/200111/6/200111/6/2001 12:00:00 AMAPASS
Added by Inspector: 430 On 11/6/2001 10:28:23 AM OK for perm occ
BLD01-02767 FIRE-Alarm Testing11/5/200111/6/200111/6/2001 12:00:00 AMAPASS
###-#### CAMI OK for perm occ 11/6/2001 10:14:34 AM
BLD01-00290 FIRE-Final Inspection11/5/200111/6/200111/6/2001 12:00:00 AMANR
Had conference with superintendant on requirements for the life/safety inspection 11/6/2001 11:21:51 AM
BLD00-01531 FIRE-Supply Line Hydro11/5/200111/6/200111/6/2001 12:00:00 AMPFAIL
3rd floor a/v's wrong candella, batteries in facp wrong, plans need resubmitted with additional detectors shown, provide map at facp, post sign on riser door, provide phone jacks, provide proper recall, provide address for remote station 11/7/2001 9:50:29 AM
BLD01-02625 FIRE-Final Inspection11/6/200111/6/200111/6/2001 12:00:00 AMPPART
Provide a audio/visual alarm device in a normally occupied area. Verify smoke detector near the fire alarm panel is a system detector. If not add detector. 11/8/2001 11:42:44 AM