Inspections for the day of: Monday, November 6, 2006.
Number of inspections: 12
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorBob Reichert
TitleELE-INSPECTOR
Phone #794-1923
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE06-04103 Electrical Rough-In11/6/200611/6/200611/6/2006 4:40:41 PMAPASS
corr made, ric ok
ELE06-04103 Rough-In Permanent Service11/4/200611/6/200611/6/2006 4:39:32 PMACANC
Reinspection. This time please call contact phone number, not office number if there are any problems preventing inspection to pass. Internet Inspection Request from: Latisha Peltier corr made, see ri
ELE06-04093 Electrical Rough-In11/6/200611/6/200611/6/2006 4:35:08 PMPPASS
Scheduled by a contractor via Hello! on 11/6/2006 at 10:11:53 AM. Contact: ###-####. walls only ok to cover
ELE06-04122 Final11/6/200611/6/200611/6/2006 3:09:18 PMPPASS
FINAL INSPECTION FOR 220 VOLT SPA CONNECTION. THANKS; Phone #: ###-#### Internet Inspection Request from: Barry Kendall ok to final
ELE06-04047 Electrical Rough-In11/6/200611/6/200611/6/2006 2:04:51 PMPPASS
Alan; Phone #: ###-#### Internet Inspection Request from: Cathy Weisshaupt corr made, walls only ok to cover
ELE06-04010 Electrical Rough-In11/6/200611/6/200611/6/2006 1:10:26 PMPPASS
Scheduled by a contractor via Hello! on 11/6/2006 at 10:14:04 AM. Contact: ###-####. walls only ok to cover
ELE06-02456 Final11/3/200611/6/200611/6/2006 10:39:39 AMANH
Phone #: ###-#### Internet Inspection Request from: Therrin Robertson called, code would not work, will have to recall
ELE06-04108 Electrical Rough-In11/3/200611/6/200611/6/2006 10:22:58 AMPCANC
Work performed by Ray Hall.; Phone #: ###-#### Internet Inspection Request from: Matt Santacruz wrong type request, see final
ELE06-04108 Final11/6/200611/6/200611/6/2006 10:22:23 AMAPASS
Work performed by Ray Hall.; Phone #: ###-#### Internet Inspection Request from: Matt Santacruz ok to final
ELE06-02455 Final11/3/200611/6/200611/6/2006 9:29:01 AMAPASS
Phone #: ###-#### Internet Inspection Request from: Therrin Robertson called for code, told contr needs faceplate for up bath, ok to final
ELE06-03604 Electrical Rough-In11/3/200611/6/200611/6/2006 8:24:10 AMAFAIL
Phone #: ###-#### Internet Inspection Request from: todd called, left message, left corr notice, nec 358.26 there shall not be over 360 degree bends in emt, 358.30(A) emt shall be securely fastened within 3' of box or termination point, 330.30(B) mc shall be securely supported within 12" of box, 300.4(A)&(D) edge of bored holes and mc cable shall be 1 1/4" from edge of framing members 250.86 all metal boxes shall be grounded
ELE06-04082 Temporary Service11/3/200611/6/200611/6/2006 8:14:49 AMAPASS
Re inspect temp pole; Phone #: ###-#### Internet Inspection Request from: todd hall corr made, t/s u/g n ok