Inspections for the day of: Monday, November 6, 2006.
Number of inspections: 26
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR06-00028 FIR-Aging Inspection11/6/200611/6/200611/7/2006 10:53:44 AM DEFR
FIR06-00589 INSP-Final Inspection11/6/200611/6/200611/7/2006 10:42:29 AMPPASS
Per field inspection by M. Timmerman, fire alarm work is acceptable, inspection passed, permit finaled.
BLD06-01798 FIRE-Final Inspection11/6/200611/6/200611/7/2006 10:40:52 AMPFAIL
Need to repair door hardware and relocate exit signage.
FIR06-00507 INSP-Final Inspection11/3/200611/6/200611/7/2006 10:40:08 AMAFAIL
Initial inspection failed due to latching supervisory signals at the panel.
MIS06-00293 FIR-Final11/6/200611/6/200611/6/2006 4:56:02 PMPFAIL
Provide covers at open electrical junction boxes and cover bare wires at two locations.
MIS06-00294 FIR-Final11/6/200611/6/200611/6/2006 4:47:33 PMPPASS
Inspection passed, contractor to provide signage at the main entry/exit prior to structural final per agreement.
MIS06-00295 FIR-Final11/6/200611/6/200611/6/2006 4:41:56 PMPPASS
Inspection passed.
BLD05-02731 FIRE-Final Inspection11/6/200611/6/200611/6/2006 4:20:46 PMAFAIL
Missing fire dept. access curb lettering, address as posted is missing one number, need to final fire sprinkler permit prior to shell life safety final.
FIR06-00550 INSP-Sprinkler Rough-in11/6/200611/6/200611/6/2006 2:43:16 PMPPART
UG fire supply line is okay to cover, contractor to provide sleeve at ductile riser for seismic clearance and cover the open end of the riser piece.
BLD06-02743 FIRE-Final Inspection11/6/200611/6/200611/6/2006 2:40:39 PMPPASS
Fire life safety passed field inspection.
FIR06-00658 INSP-Sprinkler Rough-in/Hydro11/6/200611/6/200611/6/2006 2:18:18 PMPDEFR
Wrong permit number called in, was intended for the project related UG permitted work.
FIR06-00831 INSP-Final Inspection11/6/200611/6/200611/6/2006 2:16:44 PMPPART
Relocated head is acceptable, overhead is okay to cover at the drop ceiling areas.
BLD06-02248 FIRE-Final Inspection11/6/200611/6/200611/6/2006 1:58:02 PMPPASS
Items from previous correction notice have been verified for completion, fire life safety passed.
FIR05-00402 INSP-Sprinkler Rough-in/Hydro11/4/200611/6/200611/6/2006 1:07:09 PMAPART
Repiped areas on the 3rd floor are acceptable, still need to complete tenting inspection prior to approval for cover.
FIR06-00695 INSP-Final Inspection11/3/200611/6/200611/6/2006 12:50:54 PMADEFR
Pending alarm permit final.
FIR06-00712 INSP-Final Inspection11/3/200611/6/200611/6/2006 12:50:21 PMADEFR
Pending alarm permit final.
FIR06-00694 INSP-Final Inspection11/3/200611/6/200611/6/2006 12:49:58 PMADEFR
Pending alarm permit final.
FIR06-00375 INSP-Final Inspection11/3/200611/6/200611/6/2006 12:49:19 PMADEFR
Pending alarm permit final.
FIR06-00734 INSP-Final Inspection11/3/200611/6/200611/6/2006 12:46:30 PMAPART
OH sprinkler rough-in is good for cover at the drop ceiling areas, final pending installation of ceiling tile and escutcheons.
FIR06-00235 INSP-Final Inspection11/6/200611/6/200611/6/2006 11:26:20 AMPPASS
Fire alarm permit finaled.
FIR06-00436 INSP-Final Inspection11/6/200611/6/200611/6/2006 11:25:50 AMPPASS
Fire sprinkler permit finaled.
BLD05-01823 FIRE-Final Inspection11/2/200611/6/200611/6/2006 11:25:22 AMAFAIL
Missing fire dept. access markings as indicated on fire code review notes #20 and sheet c1.1 on approved plans, one emergency light at the lower level failed to operate, remove manual flush bolts on the inactive leaf at the pair of doors in the lower level.
FIR06-00235 INSP-Alarm Testing11/2/200611/6/200611/6/2006 10:29:50 AMAPASS
Fire alarm work is acceptable, inspection passed.
BLD06-01555 FIRE-Final Inspection11/3/200611/6/200611/6/2006 9:41:06 AMAPASS
Fire life safety inspection passed. Max occupant load signs at three locations to be posted prior to structural final for verification at final field inspection.
FIR06-00730 INSP-Final Inspection11/3/200611/6/200611/6/2006 9:37:25 AMAPASS
Fire sprinkler work passed final inspection, permit finaled.
BLD06-01044 FIRE-Final Inspection11/2/200611/6/200611/6/2006 12:00:00 AMACANC
stacy--life safety fn ; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie cancelled per stacie