Inspections for the day of: Tuesday, November 6, 2012.
Number of inspections: 5
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD12-01193 FIRE-Final Inspection11/5/201211/6/201211/7/2012 12:56:09 PMPPART
Fire life safety inspection completed. Noted items include adjustments at directional exit signage, post two additional extinguishers, provide missing exit discharge light at the NE exit, relocate refrigerant alarm signage, provide EM lighting at the immediate vicinity of the north main exit, post max occupant load sign at the 2nd floor bar area, provide approved style hardware at two sliding cooler doors.
FIR12-00578 INSP-Sprinkler Rough-in11/6/201211/6/201211/6/2012 2:36:47 PMPPART
Overhead modifications and rough-in at the new office areas okayed.
FIR12-00579 INSP-Sprinkler Rough-in11/6/201211/6/201211/6/2012 2:28:50 PMPPART
Overhead work at the new office areas approved for cover.
BLD12-01806 FIRE-Final Inspection11/5/201211/6/201211/6/2012 2:27:42 PMAPASS
Items on the correction notice have been finished with the exception of door hardware at the second exit. Tenant to repair prior to structural final as agreed. Life safety passed.
FIR12-00625 INSP-Sprinkler Rough-in11/5/201211/6/201211/6/2012 2:21:02 PMAPART
See dated plan annotations for notes- common corridor missing one pendent head where grid ceiling is not installed, relocate one head adjacent to wall and finishes, basement storage room spacing needs revised, one blocked head due to new drain piping. Basement cooler and first floor kitchen area grid ceilings and heads are incomplete at this time. Okay to cover modifications above sheetrock ceilings.