Inspections for the day of: Tuesday, November 6, 2012.
Number of inspections: 3
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR12-00431 INSP-Final Inspection11/5/201211/6/201211/6/2012 3:43:30 PMPCANC
No testing was performed due to the plans needing resubmitted. I also noted door magnets that have been installed within the past week that are not connected to the fire alarm system as required per IFC 1008.1.4.4.
FIR12-00506 INSP-Final Inspection11/5/201211/6/201211/6/2012 2:33:07 PMAPASS
Permit finaled. Hood suppression system functioned correctly. I waited while the lights under the hood had been wired/tested for shutdown during alarm.
BLD11-03012 FIRE-Final Inspection11/5/201211/6/201211/6/2012 2:32:04 PMAFAIL
Items on the correctio notice have been addressed except for the fire alarm and fire sprinkler permits. I also noted door magnets that have been installed within the past week that are not connected to the fire alarm system as required per IFC 1008.1.4.4.