Inspections for the day of: Thursday, November 6, 2014.
Number of inspections: 20
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR14-00733 INSP-Final Inspection11/6/201411/6/201411/6/2014 5:21:12 PMPCANC
Overbooked
BLD14-00906 FIRE-Final Inspection11/4/201411/6/201411/6/2014 5:19:33 PMPPASS
Fire life safety inspection completed satisfactory.
FIR14-00465 INSP-Final Inspection11/6/201411/6/201411/6/2014 5:18:28 PMPPASS
Fire alarm permit work passed field inspection and testing. Contractor has provided an updated points map to be posted.
FIR14-00471 INSP-Final Inspection11/5/201411/6/201411/6/2014 5:14:01 PMAPASS
Scope of fire sprinkler work passed final inspection.
FIR14-00658 INSP-Final Inspection11/6/201411/6/201411/6/2014 3:35:29 PMPCANC
Please call 30 min prior to arrival. Phone #: ###-#### Inspection requested via web by Jeff Walton
FIR14-00351 INSP-Final Inspection11/6/201411/6/201411/6/2014 3:35:13 PMPCANC
Please call 30 min prior to arrival. Phone #: ###-#### Inspection requested via web by Jeff Walton
FIR14-00398 INSP-Sprinkler Rough-in11/5/201411/6/201411/6/2014 3:22:32 PMANH
Brandon Phone #: ###-####
FIR14-00474 INSP-Sprinkler Rough-in/Hydro11/5/201411/6/201411/6/2014 3:20:14 PMADEFR
Overbooked
BLD13-01137 FIRE-Final Inspection11/6/201411/6/201411/6/2014 3:11:36 PMPPASS
Life safety inspection passed. Need to re-post emergency fuel shutoff sign prior to final.
FIR14-00668 INSP-Sprinkler Rough-in11/5/201411/6/201411/6/2014 2:02:46 PMAFAIL
Items noted include; missing tenting at the upper level and main level garage area rec room, bathroom & storage room, noted heat tape at the supply and system main piping in breezeway-plans indicate a conditioned space, relocated main 2nd floor, provide coverage at the concealed space above the gas fired fireplace, missing aux. drain basement level, added 90s at main and supply piping, provide 175deg. heads per plan at the furnace rooms.
BLD14-02329 FIRE-Final Inspection11/6/201411/6/201411/6/2014 1:45:33 PMPDONE
Inspection request intended for project related BLD14-02181.
FIR14-00639 INSP-Final Inspection11/6/201411/6/201411/6/2014 1:44:13 PMPPASS
Final inspection passed. Fire sprinkler permit finaled.
BLD14-02181 FIRE-Final Inspection11/6/201411/6/201411/6/2014 1:43:08 PMPNR
Final pending project related fire alarm permit work, need to post building address numbers, repair one exit sign, install missing escutcheon, signs at PFE are not required, some doors and hardware are not yet installed, noted manual thumbturns on sliding doors to lease spaces.
FIR14-00586 INSP-Final Inspection11/5/201411/6/201411/6/2014 11:57:06 AMADEFR
Art Phone #: ###-####
FIR14-00734 INSP-Final Inspection11/5/201411/6/201411/6/2014 11:56:18 AMAFAIL
Audible devices to meet fire code review note item #7, visible appliances to meet review note #12. Duct detectors, SD at the new NAC tested okay.
BLD14-02370 FIRE-Final Inspection11/5/201411/6/201411/6/2014 10:18:34 AMAFAIL
AM inspection completed by T. Cobbley- items noted include; provide adequate location for the duct detector or verification min. airflow is met, missing signal transmission to offsite monitoring station, test switch is located at the roof deck.
BLD14-02850 FIRE-Final Inspection11/5/201411/6/201411/6/2014 10:10:25 AMAPASS
Fire life safety inspection completed satisfactory. Contractor to replace missing ceiling tile at the two new closets prior to structural final.
FIR14-00742 INSP-Final Inspection11/6/201411/6/201411/6/2014 10:08:27 AMAPASS
Fire sprinkler work passed final walkthrough and inspection. Permit finaled.
FIR14-00500 INSP-Sprinkler Rough-in11/5/201411/6/201411/6/2014 10:07:13 AMAPART
Noted corrections at previous inspection verified for completion. Overhead rough-in approved for ceiling cover.
FIR14-00055 INSP-Final Inspection11/5/201411/6/201411/6/2014 12:00:00 AMACANC
Dale-please call with a meet time Phone #: ###-####