ELE07-02082
| ELE-Aging Inspection | 11/6/2015 | 11/6/2015 | 11/6/2015 3:04:00 PM | | DONE |
|
|
Still under construction
|
ELE15-03593
| Electrical Rough-In | 11/5/2015 | 11/6/2015 | 11/6/2015 3:03:53 PM | P | PART |
|
|
Micah Phone #: ###-#### 250.52- Formal dining room changed to additional kitchen area. #8 SER for range has less than 10% of length in thermal insulation so 310.15(A)(2)ex applies. Minimum receptacle outlet lay out to serve counter top spaces shall be satisfied. ok to cover ceiling and pantry and upper portion of walls
|
ELE15-03514
| Electrical Rough-In | 11/4/2015 | 11/6/2015 | 11/6/2015 1:55:15 PM | P | NR |
|
|
We are requesting a wall rough-in inspection for Friday 11/6/15 in the afternoon. Our contact is Bryant @ ###-####. Thank you, Phone #: ###-#### Inspection requested via web by Clint Tate Rough in not ready at this time
|
ELE15-03419
| Final | 11/5/2015 | 11/6/2015 | 11/6/2015 12:54:07 PM | A | FAIL |
|
|
Phone #: ###-#### Inspection requested via web by Bryan McLaughlin 300.11- All cables shall be supported independant of grid. Flex in niche, 12' fixture whip. 300.15- All cables shall terminate in a box. MC above water heater. 314.25- All boxes shall have covers. 404.9- All switches shall have cover to totally enclose switch.
|
ELE15-03515
| Electrical Rough-In | 11/4/2015 | 11/6/2015 | 11/6/2015 12:32:21 PM | A | PASS |
|
|
We are requesting a rough-in inspection for Friday 11/6/15 in the AM. Our contact is Kory @ ###-####. Thank you, Phone #: ###-#### Inspection requested via web by Clint Tate Wall outlets and grid rough in ok cover
|
ELE15-03608
| Electrical Rough-In | 11/6/2015 | 11/6/2015 | 11/6/2015 11:50:36 AM | P | PASS |
|
|
Doing all warehouse and offices on 2 floors. UL listing confirmed. Rough in ok
|
ELE15-03540
| Temporary Service | 11/5/2015 | 11/6/2015 | 11/6/2015 11:35:49 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by David Nelson t/s u/g n ok
|
ELE15-02380
| Final | 11/6/2015 | 11/6/2015 | 11/6/2015 11:24:18 AM | A | FAIL |
|
|
CODE 1234 Phone #: ###-#### Inspection requested via web by Bob Glenn 110.3- Breaker shall be terminated as to manufacturers instructions. Reverse polarity on up bed circuit.
|
ELE15-03607
| Temporary Service | 11/5/2015 | 11/6/2015 | 11/6/2015 10:48:09 AM | A | PASS |
|
|
temp Phone #: ###-#### Inspection requested via web by kevin blackmon t/s u/g n ok
|
ELE15-03608
| Electrical Rough-In | 11/6/2015 | 11/6/2015 | 11/6/2015 10:33:40 AM | A | NH |
|
|
lighting retrofit rough in. We shoudl arrive approx 9am. Phone #: ###-#### Inspection requested via web by Tim Dunlop Called contact and left message. Recall when access is available
|
ELE15-03163
| Final | 11/5/2015 | 11/6/2015 | 11/6/2015 10:04:31 AM | A | NR |
|
|
Final Inspection on Banbury Cell Site. Contact Steve Hess Phone #: ###-#### Inspection requested via web by Cathy Duchek Service has not been energized yet. Will reschedule
|
ELE15-02908
| Electrical Rough-In | 11/5/2015 | 11/6/2015 | 11/6/2015 9:50:54 AM | A | PASS |
|
|
We are requesting an underground inspection at the propane station for tomorrow 11/6/15 in the AM. Our contact is Rod @ ###-####. Thank you. Phone #: ###-#### Inspection requested via web by Clint Tate Rigid stub at pump location rough in ok cover
|
ELE15-03604
| Final | 11/5/2015 | 11/6/2015 | 11/6/2015 9:28:01 AM | A | PASS |
|
|
Wiring Hot Tub Phone #: ###-#### Inspection requested via web by George Pascua Final ok
|
ELE15-03461
| Electrical Rough-In | 11/6/2015 | 11/6/2015 | 11/6/2015 9:11:42 AM | A | PASS |
|
|
This Is All Ready For Ya.. Call Me With Any Questions Or Concerns Please And Thank You Dave 919 4740 Inspection requested via web by jason shifflett All out lights and WP outdoor outlets being installed after stucco. Rough in ok cover
|
ELE15-03579
| Electrical Rough-In | 11/6/2015 | 11/6/2015 | 11/6/2015 8:41:08 AM | P | PASS |
|
|
Rough in ok cover
|