Inspections for the day of: Friday, November 6, 2015.
Number of inspections: 15
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRock A. Hudson
TitleELE-INSPECTOR
Phone #794-6794
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE07-02082 ELE-Aging Inspection11/6/201511/6/201511/6/2015 3:04:00 PM DONE
Still under construction
ELE15-03593 Electrical Rough-In11/5/201511/6/201511/6/2015 3:03:53 PMPPART
Micah Phone #: ###-#### 250.52- Formal dining room changed to additional kitchen area. #8 SER for range has less than 10% of length in thermal insulation so 310.15(A)(2)ex applies. Minimum receptacle outlet lay out to serve counter top spaces shall be satisfied. ok to cover ceiling and pantry and upper portion of walls
ELE15-03514 Electrical Rough-In11/4/201511/6/201511/6/2015 1:55:15 PMPNR
We are requesting a wall rough-in inspection for Friday 11/6/15 in the afternoon. Our contact is Bryant @ ###-####. Thank you, Phone #: ###-#### Inspection requested via web by Clint Tate Rough in not ready at this time
ELE15-03419 Final11/5/201511/6/201511/6/2015 12:54:07 PMAFAIL
Phone #: ###-#### Inspection requested via web by Bryan McLaughlin
300.11- All cables shall be supported independant of grid. Flex in niche, 12' fixture whip.
300.15- All cables shall terminate in a box. MC above water heater.
314.25- All boxes shall have covers.
404.9- All switches shall have cover to totally enclose switch.
ELE15-03515 Electrical Rough-In11/4/201511/6/201511/6/2015 12:32:21 PMAPASS
We are requesting a rough-in inspection for Friday 11/6/15 in the AM. Our contact is Kory @ ###-####. Thank you, Phone #: ###-#### Inspection requested via web by Clint Tate Wall outlets and grid rough in ok cover
ELE15-03608 Electrical Rough-In11/6/201511/6/201511/6/2015 11:50:36 AMPPASS
Doing all warehouse and offices on 2 floors. UL listing confirmed. Rough in ok
ELE15-03540 Temporary Service11/5/201511/6/201511/6/2015 11:35:49 AMAPASS
Phone #: ###-#### Inspection requested via web by David Nelson t/s u/g n ok
ELE15-02380 Final11/6/201511/6/201511/6/2015 11:24:18 AMAFAIL
CODE 1234 Phone #: ###-#### Inspection requested via web by Bob Glenn
110.3- Breaker shall be terminated as to manufacturers instructions. Reverse polarity on up bed circuit.
ELE15-03607 Temporary Service11/5/201511/6/201511/6/2015 10:48:09 AMAPASS
temp Phone #: ###-#### Inspection requested via web by kevin blackmon
t/s u/g n ok
ELE15-03608 Electrical Rough-In11/6/201511/6/201511/6/2015 10:33:40 AMANH
lighting retrofit rough in. We shoudl arrive approx 9am. Phone #: ###-#### Inspection requested via web by Tim Dunlop Called contact and left message. Recall when access is available
ELE15-03163 Final11/5/201511/6/201511/6/2015 10:04:31 AMANR
Final Inspection on Banbury Cell Site. Contact Steve Hess Phone #: ###-#### Inspection requested via web by Cathy Duchek Service has not been energized yet. Will reschedule
ELE15-02908 Electrical Rough-In11/5/201511/6/201511/6/2015 9:50:54 AMAPASS
We are requesting an underground inspection at the propane station for tomorrow 11/6/15 in the AM. Our contact is Rod @ ###-####. Thank you. Phone #: ###-#### Inspection requested via web by Clint Tate Rigid stub at pump location rough in ok cover
ELE15-03604 Final11/5/201511/6/201511/6/2015 9:28:01 AMAPASS
Wiring Hot Tub Phone #: ###-#### Inspection requested via web by George Pascua Final ok
ELE15-03461 Electrical Rough-In11/6/201511/6/201511/6/2015 9:11:42 AMAPASS
This Is All Ready For Ya.. Call Me With Any Questions Or Concerns Please And Thank You Dave 919 4740 Inspection requested via web by jason shifflett
All out lights and WP outdoor outlets being installed after stucco. Rough in ok cover
ELE15-03579 Electrical Rough-In11/6/201511/6/201511/6/2015 8:41:08 AMPPASS
Rough in ok cover