BLD17-02584
| FIRE-Final Inspection | 11/2/2017 | 11/6/2017 | 11/6/2017 3:31:08 PM | A | PASS |
|
|
Fire sprinkler inspection complete, fire alarm inspection complete, fire extinguishers are in place with current inspection tags. Final life fire safety inspection for area of work passed/complete.
|
BLD17-02186
| FIRE-Final Inspection | 11/2/2017 | 11/6/2017 | 11/6/2017 3:30:54 PM | A | PASS |
|
|
Fire sprinkler inspection complete, fire alarm inspection complete, fire extinguishers are in place with current inspection tags. Final life fire safety inspection for area of work passed/complete.
|
BLD17-00970
| FIRE-Final Inspection | 11/2/2017 | 11/6/2017 | 11/6/2017 3:30:39 PM | A | PASS |
|
|
Fire sprinkler inspection complete, fire alarm inspection complete, fire extinguishers are in place with current inspection tags. Final life fire safety inspection for area of work passed/complete.
|
FIR17-00532
| INSP-Final Inspection | 11/3/2017 | 11/6/2017 | 11/6/2017 3:09:07 PM | P | PASS |
|
|
Final fire alarm inspection for area of work passed/complete.
|
FIR17-00524
| INSP-Final Inspection | 11/3/2017 | 11/6/2017 | 11/6/2017 3:08:52 PM | P | PASS |
|
|
Final fire alarm inspection for area of work passed/complete.
|
FIR17-00517
| INSP-Final Inspection | 11/6/2017 | 11/6/2017 | 11/6/2017 3:08:07 PM | P | PASS |
|
|
Final fire sprinkler inspection for area of work passed/complete.
|
FIR17-00257
| INSP-Final Inspection | 11/6/2017 | 11/6/2017 | 11/6/2017 3:07:51 PM | P | PASS |
|
|
Final fire sprinkler inspection for area of work passed/complete.
|
FIR17-00516
| INSP-Final Inspection | 11/6/2017 | 11/6/2017 | 11/6/2017 3:07:34 PM | P | PASS |
|
|
Final fire sprinkler inspection for area of work passed/complete.
|
FIR17-00336
| INSP-Final Inspection | 11/6/2017 | 11/6/2017 | 11/6/2017 3:07:19 PM | P | PASS |
|
|
Final fire sprinkler inspection for area of work passed/complete.
|
FIR17-00517
| INSP-Sprinkler Rough-in | 11/6/2017 | 11/6/2017 | 11/6/2017 3:06:42 PM | P | PASS |
|
|
Rough to cover inspection for area of work complete, area of work approved for cover.
|
FIR17-00257
| INSP-Sprinkler Rough-in | 11/6/2017 | 11/6/2017 | 11/6/2017 3:06:23 PM | P | PASS |
|
|
Rough to cover inspection for area of work complete, area of work approved for cover.
|
FIR17-00516
| INSP-Sprinkler Rough-in | 11/6/2017 | 11/6/2017 | 11/6/2017 3:06:03 PM | P | PASS |
|
|
Rough to cover inspection for area of work complete, area of work approved for cover.
|
FIR17-00336
| INSP-Sprinkler Rough-in | 11/6/2017 | 11/6/2017 | 11/6/2017 3:05:44 PM | P | PASS |
|
|
Rough to cover inspection for area of work complete, area of work approved for cover.
|
FIR17-00047
| INSP-Sprinkler Rough-in | 11/6/2017 | 11/6/2017 | 11/6/2017 2:17:12 PM | P | CANC |
|
|
Inspection request will be rescheduled due to shceduling issues for inspection request.
|
FIR17-00435
| INSP-Sprinkler Rough-in/Hydro | 11/6/2017 | 11/6/2017 | 11/6/2017 12:49:42 PM | P | PASS |
|
|
Underground supply hydrostatc test complete.
|
BLD17-03817
| FIRE-Final Inspection | 11/3/2017 | 11/6/2017 | 11/6/2017 12:22:28 PM | A | FAIL |
|
|
Surface mount slide bolt lock on exterior exit door from tenant space to outside stairs needs to be removed. Fire extinguisher needs inspected/serviced and tagged accordingly. Emergency egress ligh that is located in the corridor of the tenant space needs to be serviced, emergrncy light was in-operable at time of inspection.
|
FIR17-00042
| INSP-Sprinkler Rough-in/Hydro | 11/3/2017 | 11/6/2017 | 11/6/2017 11:58:44 AM | A | CANC |
|
|
Could not connect with point of contact, Clarence Phone #: ###-####, inspection request will need to be rescheduled.
|
FIR17-00519
| INSP-Sprinkler Rough-in | 11/3/2017 | 11/6/2017 | 11/6/2017 11:54:00 AM | A | PASS |
|
|
Rough to cover inspection for area of work complete, area of work approved for cover.
|
BLD17-03270
| FIRE-Final Inspection | 11/3/2017 | 11/6/2017 | 11/6/2017 11:50:43 AM | A | PASS |
|
|
No fire sprinkler modofcations, no fire alarm modifications, fire extinguisher will be mounted in discussed location. Final life fire safety inspection for area of work passed/complete.
|
FIR17-00598
| INSP-Final Inspection | 11/3/2017 | 11/6/2017 | 11/6/2017 11:40:27 AM | A | PASS |
|
|
Final inspection for area of work demo complete. Noted that the building did not have heat when inspection for demo work was performed, the building needs to be maintained at a minimum of 40 degrees per fire sprinkler code, heat needs to be maintained to protect the wet type fire sprinkler system from freezing.
|
BLD17-03697
| FIRE-Final Inspection | 11/3/2017 | 11/6/2017 | 11/6/2017 11:23:50 AM | A | PART |
|
|
No fire alarm modifications, fire extinguishers are in common areas with current inspection tags. TCO for life fire safety is authorized for 30 days per conversation with Scott Arellano, TCO is contingent on the fire sprinkler modifications being completed. Once fire sprinkler work is completed then life fire safey can be finaled.
|
FIR17-00595
| INSP-Final Inspection | 11/6/2017 | 11/6/2017 | 11/6/2017 10:42:19 AM | A | PASS |
|
|
Final inspection for fire alarm demo work complete.
|
BLD17-02655
| FIRE-Final Inspection | 11/3/2017 | 11/6/2017 | 11/6/2017 9:51:19 AM | A | FAIL |
|
|
Emergency lighting needs to be installed per city approved drawings, emergency lighting needs to be installed in the north hallway. Exterior emergency lighting for exit discharge needs to be installed. Exit signs need to be serviced, internal illumination was not working at time of inspection.
|
FIR17-00575
| INSP-Final Inspection | 11/6/2017 | 11/6/2017 | 11/6/2017 9:47:11 AM | A | PASS |
|
|
Final fire sprinkler inspection passed/complete.
|
BLD17-01694
| FIRE-Final Inspection | 11/3/2017 | 11/6/2017 | 11/6/2017 8:54:55 AM | A | PART |
|
|
Fire sprinkler inspection complete, racking permit complete, fire extinguishers are in place with current inspection tags, fire alarms will be completed at a later date (FIR17-00649, fire sprinkler system is being monitored at time of inspection). TCO for life fire safety authorized for 30 days per conversation with Scott Arellano, TCO is contingent on fire alarm inspection being completed and passed.
|