Inspections for the day of: Tuesday, November 6, 2018.
Number of inspections: 18
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJack Reynolds
TitleMEC INSPECTOR
Phone #208-803-2395
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
MEC18-05034 Final11/6/201811/6/201811/6/2018 3:57:18 PMPCANC
Kevin Phone #: ###-####- should have been a R/I
MEC18-05034 Rough-in11/6/201811/6/201811/6/2018 3:57:00 PMPPART
Kevin Phone #: ###-####-
ducting in floor ok- ok for cover
MEC18-05324 Rough-in11/6/201811/6/201811/6/2018 3:24:16 PMPFAIL
gas and flue test also Phone #: ###-#### Inspection requested via web by Dave Sorensen
- 20lb gas pressure test ok- 5lb flue pressure test ok-
- failed need city approved Man J stamped and onsite- range exhaust needs nails plates both sides of bottom plate
MEC18-05106 Rough-in11/5/201811/6/201811/6/2018 2:51:13 PMPFAIL
1369 - lock-box
Furnace and crawl replacement. Phone #: ###-#### Inspection requested via web by Bryan Palmer- need to have a Man J performed for new system- B vent for furnace in the attic needs 1 " clearances- need to add duct work/ dryer vent/ range vent/exhaust fans to permit- need to seal supply boots in the floor- no access to attic to check full work
MEC18-03857 Final11/6/201811/6/201811/6/2018 2:05:20 PMPPASS
Lock box next to front door. Code is 2010 Phone #: ###-#### Inspection requested via web by Floyd Floyd Peek- final ok
PLM18-04633 Water Heater Final11/2/201811/6/201811/6/2018 1:46:06 PMPNR
Please call technician Chris Matos at ###-#### prior to arrival Phone #: ###-#### Inspection requested via web by Andrea Grigsby
- not ready crew still working
MEC18-05266 Final11/2/201811/6/201811/6/2018 1:45:48 PMPNR
Please call technician Chris Matos at ###-#### prior to arrival.
Thank you Phone #: ###-#### Inspection requested via web by Andrea Grigsby- not ready crew still working
PLM18-04673 Water Heater Final11/5/201811/6/201811/6/2018 1:45:20 PMPPASS
There should be someone home to give you access, if not call number above. Phone #: ###-#### Inspection requested via web by Vaughn Carlson- final ok
MEC18-04363 Final11/5/201811/6/201811/6/2018 1:05:22 PMPNR
Access: 5674
Adam: ###-#### Phone #: ###-#### Inspection requested via web by Frank Marturello- not ready
MEC18-03354 Final11/5/201811/6/201811/6/2018 11:15:56 AMAPASS
CO''s were added and penetration sealed and sent picture directly but I never requested the final again, I thought you passed this previously with corrections needed. I''m sorry for that, my fault, I''m requesting this to be finaled so client can get his rebate. I left my number if any concerns or questions, my name is Steve Dale Phone #: ###-#### Inspection requested via web by Rick Montgomery
- final ok
MEC18-05303 Rough-in11/5/201811/6/201811/6/2018 10:45:22 AMAPASS
Cover for Nanometrics/Nikon - please call Curt Miller prior to arrival if possible ###-#### Phone #: ###-#### Inspection requested via web by Heather Gransbery- R/I ok
MEC18-04294 Final11/5/201811/6/201811/6/2018 10:08:52 AMAPASS
Clint ###-#### Phone #: ###-#### Inspection requested via web by Mike Almanza- fireplace final ok
MEC18-02901 Final11/5/201811/6/201811/6/2018 9:50:14 AMAPASS
Phone #: ###-#### Inspection requested via web by Dawn Kalsbeek- final ok
MEC18-00605 Mec-Aging Inspection11/6/201811/6/201811/6/2018 9:12:59 AM FAIL
no final inspection scheduled
MEC18-00609 Mec-Aging Inspection11/6/201811/6/201811/6/2018 9:12:38 AM FAIL
no inspection scheduled
MEC17-05119 Mec-Aging Inspection11/6/201811/6/201811/6/2018 9:12:19 AM FAIL
no inspection scheduled
MEC18-04705 Rough-in11/5/201811/6/201811/6/2018 9:11:01 AMAFAIL
Terek Phone #: ###-####
- need city approved Man J stamped and onsite
- toe kick in kitcken needs ran out from under kitcken cabinet
-5lb flue pressure test fail
- supply trunk going upstairs has a kink at a 90 degree turn that needs fixed
MEC18-04705 Pressure Test11/5/201811/6/201811/6/2018 9:08:32 AMAPART
Terek Phone #: ###-####- 5lb flue pressure test fail gauge was under 5lb- 20lb gas pressure test ok