Inspections for the day of: Thursday, November 7, 2002.
Number of inspections: 8
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD02-02095 FIRE-Final Inspection11/6/200211/7/200211/7/2002 12:00:00 AMAFAIL
Fire sprinkler work without a permit.
Provide city approved fire sprinkler drawings, contractor stated that the existing sprinkler heads are spaced 18 x 18 but he is spacing the pendant in the sunroom 20 x 20 fed from 3/4" pipe. A sidewall sprinkler head will need to be added in the garage along the new wall 11/7/2002 10:53:01 AM
BLD02-00751 FIRE-Conference11/6/200211/7/200211/7/2002 12:00:00 AMADONE
spoke with the contractor about curb painting, fire extinguisher placement and door hardware. 11/7/2002 9:42:00 AM
FIR02-00144 INSP-Final Inspection11/6/200211/7/200211/7/2002 12:00:00 AMAFAIL
provide revised battery calcs for the 24ah batteries, provide labels and zone map 11/7/2002 9:43:28 AM
BLD02-01985 FIRE-Final Inspection11/6/200211/7/200211/7/2002 12:00:00 AMAPASS
###-#### brett
BLD02-01985 FIRE-Final Inspection11/6/200211/7/200211/7/2002 12:00:00 AMAPASS
###-#### brett
BLD02-02200 FIRE-Final Inspection11/7/200211/7/200211/7/2002 12:00:00 AMPFAIL
provide one 2-A10BC fire extinguisher with current inspection tag mounted with handle at 48" in a normal path of travel. See note #3, repair exit signs in path of eress from tenant space to building exterior then test exit signs. Provide City of Boise approved fire alarm plans. See note #2. Replace the insulation above the sprinkler uprights along the north half of the new demising wall. Provide ceiling tile at the sprinkler pendants and replace the missing canopies. Remove the dry wall splatter from the sprinkler pendants. Provide a suite address for tenant and provide a key for the "knox box" 11/7/2002 1:53:58 PM
FIR02-00403 INSP-Final Inspection11/7/200211/7/200211/7/2002 12:00:00 AMPFAIL
insulation needs to be installed above the sprinkler uprights along the new demising wall and provide tiles and canopies at sprinkler pendants prior to finaling
FIR02-00403 INSP-Final Inspection11/7/200211/7/200211/7/2002 12:00:00 AMPFAIL
insulation needs to be installed above the sprinkler uprights along the new demising wall and provide tiles and canopies at sprinkler pendants prior to finaling