Inspections for the day of: Monday, November 7, 2005.
Number of inspections: 15
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorBob Reichert
TitleELE-INSPECTOR
Phone #794-1923
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE05-02402 Final11/7/200511/7/200511/7/2005 5:22:53 PMPFAIL
justin; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles called contr, left corr notice, 210.52(C)(1) recpt shall be added by range, 210.52(A)(2) garage recpts shall be gfci, 422.31(B) dishwasher shall have lockout provided at breaker, 408.4 circuit 9 shall be explicit, 406.5 recpt faceplates shall seat against mounting surface,110.13(A) front recpt cover shall be secure and operate
ELE05-04010 Electrical Rough-In11/7/200511/7/200511/7/2005 5:18:30 PMPFAIL
kelly; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles no panel set, talked to elect, left corr notice, 210.52(A)(2) recpt shall be added in entry area wall, 210.52(F) recpt shall be added at rear of dwelling, 314.20 boxes shall be flush with combustible material, 334.30 nm cable shall be supported within 12" of boxs, 300.4(A)(1) edge of bored hole shall be 1 1/4" from edgfe of framing member, 800.133(A)(1) comm cable shall not be run with power cables
ELE05-03000 Final11/7/200511/7/200511/7/2005 5:13:45 PMPPASS
###-#### - don ok to final
ELE05-03000 Permanent Service11/7/200511/7/200511/7/2005 4:27:55 PMPPASS
###-#### - don p/s done, job done, ok to final
ELE05-03938 Final11/2/200511/7/200511/7/2005 4:24:26 PMPPASS
WIRING FOR HOTTUB ON SECOND DECK. PLEASE CALL CUSTOMER STEVE COPE @ ###-#### TO SCHEDULE; Phone #: ###-#### Internet Inspection Request from: BRIAN KEITH ok to final
ELE05-02615 Electrical Rough-In11/7/200511/7/200511/7/2005 2:07:19 PMPCANC
Phone #: ###-#### Internet Inspection Request from: JENNY EMEL see p/s
ELE05-04025 Permanent Service11/7/200511/7/200511/7/2005 12:31:42 PMPPASS
###-#### - don called contr to plug hole, chg gec. ok to cover u/g to recpt. p/s u/g n ok
ELE03-03643 Electrical Rough-In11/4/200511/7/200511/7/2005 10:19:46 AMACANC
request first thing in am//scott; Phone #: ###-#### Internet Inspection Request from: Letitia Mesa cust called to postpone
ELE05-03147 Final11/5/200511/7/200511/7/2005 9:02:29 AMAPASS
Scheduled by a contractor via Hello! on 11/5/2005 at 6:21:12 PM. Contact: ###-####. ok to final
ELE05-03278 Electrical Rough-In11/4/200511/7/200511/7/2005 8:39:17 AMACANC
see rip
ELE05-00855 Electrical Rough-In11/4/200511/7/200511/7/2005 8:18:23 AMAPASS
CONTACT: LYLE DEAN 1ST FLOOR INSPECTION; Phone #: ###-#### Internet Inspection Request from: Deb McCoy ok to cover poured in u/g by elect room
ELE03-03037 Final11/7/200511/7/200511/7/2005 7:41:17 AMAPASS
final evaluation done 11-02-05, field report to be sent. witnessed final tagging of equipment. ok to final Bob R.
ELE05-03472 Final11/7/200511/7/200511/7/2005 12:00:00 AMAPART
part final ok, no cards on site, open item is curb by 480V panel.
ELE05-02615 Permanent Service11/7/200511/7/200511/7/2005 12:00:00 AMPPASS
Phone #: ###-#### Internet Inspection Request from: JENNY EMEL p/s u/g n ok
ELE05-03278 Rough-In Permanent Service11/7/200511/7/200511/7/2005 12:00:00 AMPPASS
ri walls only ok, p/s u/g n ok