Inspections for the day of: Tuesday, November 7, 2006.
Number of inspections: 22
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJack Frank
TitleELE-INSPECTOR
Phone #794-1930
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE06-03171 Electrical Rough-In11/7/200611/7/200611/7/2006 2:55:09 PMPPASS
Phone #: ###-#### Internet Inspection Request from: Curtis Dunham ok
ELE06-04149 Permanent Service11/7/200611/7/200611/7/2006 2:54:53 PMPFAIL
roy; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles called corr. needs dead front for p/s, 250.122 needs #6 copper equip grd to trailer, 110.12(A) seal KOs, also job not ready
ELE06-04150 Permanent Service11/7/200611/7/200611/7/2006 2:52:35 PMPPASS
roy; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles p/s u/g rec ok
ELE06-04150 Final11/7/200611/7/200611/7/2006 2:52:08 PMPPASS
roy; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles
ELE06-04135 Rough-In Permanent Service11/6/200611/7/200611/7/2006 2:14:48 PMPFAIL
Scheduled by a contractor via Hello! on 11/6/2006 at 4:23:37 PM. Contact: ###-####. see permit #4131 for corr. info.
ELE06-04133 Rough-In Permanent Service11/6/200611/7/200611/7/2006 2:14:13 PMPFAIL
Scheduled by a contractor via Hello! on 11/6/2006 at 4:22:18 PM. Contact: ###-####. see permit#4131 for corr. info
ELE06-04130 Rough-In Permanent Service11/6/200611/7/200611/7/2006 2:13:37 PMPNR
Scheduled by a contractor via Hello! on 11/6/2006 at 4:21:03 PM. Contact: ###-####. needs ID at meter
ELE06-04132 Rough-In Permanent Service11/6/200611/7/200611/7/2006 2:12:51 PMPFAIL
Scheduled by a contractor via Hello! on 11/6/2006 at 4:19:44 PM. Contact: ###-####. see permit #ele06-04131 for corr.
ELE06-04131 Rough-In Permanent Service11/6/200611/7/200611/7/2006 2:11:45 PMPFAIL
Scheduled by a contractor via Hello! on 11/6/2006 at 4:18:24 PM. Contact: ###-####. corr. 110.3(B) all vacuum outles shall be feed with non-metallic methods of wiring, 348.26 over over 360 degrees of bends in a/c flex, 300.4(D) 11/4" for flex parallel to studs ID meter called
ELE06-02362 Final11/7/200611/7/200611/7/2006 12:52:47 PMPNR
steven ; Phone #: ###-#### still needs outside outlet installed called
ELE06-02491 Final11/6/200611/7/200611/7/2006 11:51:03 AMAPASS
Phone #: ###-#### Internet Inspection Request from: Terrie Dickson ok
ELE06-03569 Final11/7/200611/7/200611/7/2006 9:25:44 AMANR
reinspection; Phone #: ###-#### Internet Inspection Request from: DJ Carman fee due corr. not made
ELE06-04142 Electrical Rough-In11/6/200611/7/200611/7/2006 9:04:28 AMANH
jeff; Phone #: ###-#### Internet Inspection Request from: Patricia Smith called notice posted
ELE06-03596 Final11/7/200611/7/200611/7/2006 8:41:08 AMAPASS
Steve Sellers, use front door to enter please.; Phone #: ###-#### Internet Inspection Request from: steve sellers ok
ELE06-03780 Permanent Service11/6/200611/7/200611/7/2006 8:19:40 AMACANC
jack -- underground ; Phone #: ###-#### or ###-#### Internet Inspection Request from: Patricia Smith see added r/i
ELE06-03780 Electrical Rough-In11/7/200611/7/200611/7/2006 8:18:52 AMAPASS
jack -- underground ; Phone #: ###-#### or ###-#### Internet Inspection Request from: Patricia Smith ok corr. made
ELE06-00826 ELE-Aging Inspection11/7/200611/7/200611/7/2006 7:35:25 AM CANC
ELE06-00826 Final11/7/200611/7/200611/7/2006 7:35:14 AMAPASS
done by 370 09-07-06
ELE06-02413 ELE-Aging Inspection11/7/200611/7/200611/7/2006 7:34:07 AM CANC
ELE06-03110 ELE-Aging Inspection11/7/200611/7/200611/7/2006 7:33:25 AM PART
wsuc
ELE06-02362 Electrical Rough-In11/7/200611/7/200611/7/2006 12:00:00 AMPCANC
steven ; Phone #: ###-#### Internet Inspection Request from: Patricia Smith
ELE06-03863 Rough-In Permanent Service11/6/200611/7/200611/6/2006 1:27:06 PMAPASS
Phone #: ###-#### Internet Inspection Request from: Patricia Smith walls floor and ceilings ok p/s u/g new ok