Inspections for the day of: Tuesday, November 7, 2006.
Number of inspections: 13
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorBob Reichert
TitleELE-INSPECTOR
Phone #794-1923
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE06-01478 ELE-Aging Inspection11/7/200611/7/200611/7/2006 4:12:56 PM DONE
suc
ELE06-01801 ELE-Aging Inspection11/7/200611/7/200611/7/2006 4:12:36 PM DONE
suc
ELE06-02605 Final11/7/200611/7/200611/7/2006 4:11:56 PMPCANC
butch ; Phone #: ###-#### Internet Inspection Request from: Patricia Smith called, left message to call to set up an appointment to see job
ELE06-01263 Final11/7/200611/7/200611/7/2006 4:10:44 PMPFAIL
Scheduled by a contractor via Hello! on 11/7/2006 at 10:47:37 AM. Contact: ###-####. called, left corr notice, nec 110.12(A) unused openings shall be closed, 408.4 circuit directory shall be clear, concise, and complete, 680.26(B)(4) pump motors shall be bonded
ELE06-02992 Final11/7/200611/7/200611/7/2006 3:00:43 PMPPASS
thomas ; Phone #: ###-#### Internet Inspection Request from: Patricia Smith corr made, ok to final
ELE06-03927 Rough-In Permanent Service11/7/200611/7/200611/7/2006 2:13:32 PMPFAIL
butch - note: underground service insp. ; Phone #: ###-#### Internet Inspection Request from: Patricia Smith called, left message, nec 300.5 u/g not min 18" or 24" if under driveway, looks like should be public works for street lights
ELE06-02887 Electrical Rough-In11/6/200611/7/200611/7/2006 1:50:27 PMPPASS
Scheduled by a contractor via Hello! on 11/6/2006 at 3:34:35 PM. Contact: ###-####. ok to cover dropped ceilings, wrote corr notice for 210.52, show window recpts
ELE06-03027 Electrical Rough-In11/7/200611/7/200611/7/2006 1:04:55 PMPPART
dennis; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles north and east walls only ok to cover, need to look at center, west and south areas for strapping, ko seals, 1 1/4" for mc , ground boxes, make-up
ELE06-03724 Electrical Rough-In11/7/200611/7/200611/7/2006 12:58:48 PMPNH
Billie ###-####//requests either early pm or late pm because she has to pick up kids at 2:30 called, owner not living there, could not be there for a while, inspector said to request another inspection when owner available, such as in morning
ELE06-04144 Permanent Service11/6/200611/7/200611/7/2006 9:59:06 AMAFAIL
brandon; Phone #: ###-#### Internet Inspection Request from: Cathy called, left message, left corr notice, nec 312.5 all conductors entering enclosures shall have abrasion protection, 408.4 circuit directory shall be complete, clear, concise, and specific, 110.26(A) clear work space shall be provided per code(1) depth and (3) height, 250.140 range and dryer recpts and cords shall be grounded,BCC address shall be posted and correct
ELE06-04143 Permanent Service11/6/200611/7/200611/7/2006 9:43:25 AMAFAIL
brandon; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles called, left message, left corr notice, nec 312.5 all conductors entering enclosures shall have abrasion protection, 110.12(C) there shall be no broken parts (hasp on j-box), 314.25 j-box cover shall be secured, 250.52(A)(1) metal water pipe shall be used as grounding electrode, 250.140 range and dryer recpts and cords shall be grounded,BCC address shall be posted and correct
ELE06-04011 Electrical Rough-In11/6/200611/7/200611/7/2006 9:25:17 AMAPASS
Please call Jim w/ Doherty @ ###-#### 1/2 hr before for access. Scheduled by Heather w/ Doherty; Phone #: ###-#### Internet Inspection Request from: Heather Packer ric ok
ELE06-04110 Electrical Rough-In11/6/200611/7/200611/7/2006 8:34:34 AMAPASS
Phone #: ###-#### Internet Inspection Request from: Kerri Hamilton walls only ok to cover