ELE06-01478
| ELE-Aging Inspection | 11/7/2006 | 11/7/2006 | 11/7/2006 4:12:56 PM | | DONE |
|
|
suc
|
ELE06-01801
| ELE-Aging Inspection | 11/7/2006 | 11/7/2006 | 11/7/2006 4:12:36 PM | | DONE |
|
|
suc
|
ELE06-02605
| Final | 11/7/2006 | 11/7/2006 | 11/7/2006 4:11:56 PM | P | CANC |
|
|
butch ; Phone #: ###-#### Internet Inspection Request from: Patricia Smith called, left message to call to set up an appointment to see job
|
ELE06-01263
| Final | 11/7/2006 | 11/7/2006 | 11/7/2006 4:10:44 PM | P | FAIL |
|
|
Scheduled by a contractor via Hello! on 11/7/2006 at 10:47:37 AM. Contact: ###-####. called, left corr notice, nec 110.12(A) unused openings shall be closed, 408.4 circuit directory shall be clear, concise, and complete, 680.26(B)(4) pump motors shall be bonded
|
ELE06-02992
| Final | 11/7/2006 | 11/7/2006 | 11/7/2006 3:00:43 PM | P | PASS |
|
|
thomas ; Phone #: ###-#### Internet Inspection Request from: Patricia Smith corr made, ok to final
|
ELE06-03927
| Rough-In Permanent Service | 11/7/2006 | 11/7/2006 | 11/7/2006 2:13:32 PM | P | FAIL |
|
|
butch - note: underground service insp. ; Phone #: ###-#### Internet Inspection Request from: Patricia Smith called, left message, nec 300.5 u/g not min 18" or 24" if under driveway, looks like should be public works for street lights
|
ELE06-02887
| Electrical Rough-In | 11/6/2006 | 11/7/2006 | 11/7/2006 1:50:27 PM | P | PASS |
|
|
Scheduled by a contractor via Hello! on 11/6/2006 at 3:34:35 PM. Contact: ###-####. ok to cover dropped ceilings, wrote corr notice for 210.52, show window recpts
|
ELE06-03027
| Electrical Rough-In | 11/7/2006 | 11/7/2006 | 11/7/2006 1:04:55 PM | P | PART |
|
|
dennis; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles north and east walls only ok to cover, need to look at center, west and south areas for strapping, ko seals, 1 1/4" for mc , ground boxes, make-up
|
ELE06-03724
| Electrical Rough-In | 11/7/2006 | 11/7/2006 | 11/7/2006 12:58:48 PM | P | NH |
|
|
Billie ###-####//requests either early pm or late pm because she has to pick up kids at 2:30 called, owner not living there, could not be there for a while, inspector said to request another inspection when owner available, such as in morning
|
ELE06-04144
| Permanent Service | 11/6/2006 | 11/7/2006 | 11/7/2006 9:59:06 AM | A | FAIL |
|
|
brandon; Phone #: ###-#### Internet Inspection Request from: Cathy called, left message, left corr notice, nec 312.5 all conductors entering enclosures shall have abrasion protection, 408.4 circuit directory shall be complete, clear, concise, and specific, 110.26(A) clear work space shall be provided per code(1) depth and (3) height, 250.140 range and dryer recpts and cords shall be grounded,BCC address shall be posted and correct
|
ELE06-04143
| Permanent Service | 11/6/2006 | 11/7/2006 | 11/7/2006 9:43:25 AM | A | FAIL |
|
|
brandon; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles called, left message, left corr notice, nec 312.5 all conductors entering enclosures shall have abrasion protection, 110.12(C) there shall be no broken parts (hasp on j-box), 314.25 j-box cover shall be secured, 250.52(A)(1) metal water pipe shall be used as grounding electrode, 250.140 range and dryer recpts and cords shall be grounded,BCC address shall be posted and correct
|
ELE06-04011
| Electrical Rough-In | 11/6/2006 | 11/7/2006 | 11/7/2006 9:25:17 AM | A | PASS |
|
|
Please call Jim w/ Doherty @ ###-#### 1/2 hr before for access. Scheduled by Heather w/ Doherty; Phone #: ###-#### Internet Inspection Request from: Heather Packer ric ok
|
ELE06-04110
| Electrical Rough-In | 11/6/2006 | 11/7/2006 | 11/7/2006 8:34:34 AM | A | PASS |
|
|
Phone #: ###-#### Internet Inspection Request from: Kerri Hamilton walls only ok to cover
|