Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR06-00687 INSP-Final Inspection11/6/200611/7/200611/13/2006 1:17:57 PMAPASS
Fire sprinkler permit finaled.
MIS06-00287 FIR-Final11/6/200611/7/200611/8/2006 8:31:54 AMACANC
No time available to complete this inspection today.
FIR06-00065 INSP-Final Inspection11/6/200611/7/200611/7/2006 3:51:20 PMPPART
Items from previous inspection verified for completion, forward flow completed, okay for final when ball drip and FDC caps are installed.
FIR06-00836 INSP-Sprinkler Rough-in11/7/200611/7/200611/7/2006 3:45:25 PMPPART
OH rough-in is acceptable.
BLD05-03029 BLD-Final11/7/200611/7/200611/7/2006 3:44:22 PMPFAIL
SD within 20' of a cooking appliance must be "push to silence" or of the photoelectric type, SD must not be located within 3' of an adjacent opening to a room containing a shower, detectors at two locations need the dust covers removed before final.
BLD05-03335 FIRE-Final Inspection11/7/200611/7/200611/7/2006 2:31:43 PMPFAIL
The project related fire sprinkler permit must be approved and finaled prior to building life safety final.
BLD05-03029 FIRE-Final Inspection11/6/200611/7/200611/7/2006 2:30:14 PMPDEFR
FIR06-00807 INSP-Sprinkler Rough-in11/7/200611/7/200611/7/2006 2:26:58 PMPPART
Overhead rough-in is acceptabe pending verification the original system design can support up to three heads off 1" pipe as newly installed at one loction in the front canopy area.
FIR06-00137 INSP-Final Inspection11/7/200611/7/200611/7/2006 2:21:56 PMPPASS
Inspected resubmittals, verified UG supply is approved for the 4" size installed, c/n items have been amended, noted to contractor to provide signage at the door to the riser room.
FIR06-00672 INSP-Sprinkler Rough-in11/7/200611/7/200611/7/2006 2:05:22 PMPPART
Inspection for a portion of the drop ceiling areas at the main seating area and the kitchen prep. hallway are okay for cover, several pendent heads at scattered locations are not yet installed.
BLD06-01798 FIRE-Final Inspection11/6/200611/7/200611/7/2006 2:01:27 PMAPASS
Items on c/n have been completed, fire life safety inspection passed.
FIR06-00855 INSP-Final Inspection11/6/200611/7/200611/7/2006 2:00:37 PMAPASS
Fire sprinkler work completed satisfactory, permit finaled.
FIR06-00808 INSP-Sprinkler Rough-in11/7/200611/7/200611/7/2006 12:56:54 PMPPART
OH rough-in at the drop ceiling areas only are good for cover.
BLD06-00769 FIRE-Final Inspection11/6/200611/7/200611/7/2006 12:55:39 PMAPART
Required corrections for unit 315 second floor have been verified for completion.
BLD06-01492 FIRE-Final Inspection11/7/200611/7/200611/7/2006 11:15:07 AMAPASS
Fire life safety is acceptable.
FIR06-00588 INSP-Final Inspection11/7/200611/7/200611/7/2006 11:14:34 AMPPASS
Fire sprinkler permit finaled.
FIR06-00072 FIR-Aging Inspection11/7/200611/7/200611/7/2006 10:55:27 AM DONE
Scope of work as described has been completed by a different contractor.
FIR06-00712 INSP-Final Inspection11/6/200611/7/200611/7/2006 10:50:52 AMAPASS
One missing escutcheon installed while on site, fire sprinkler work completed satisfactory, permit finaled.
FIR06-00695 INSP-Final Inspection11/6/200611/7/200611/7/2006 10:49:57 AMAPASS
Fire sprinkler passed inspection, permit finaled.
FIR06-00694 INSP-Final Inspection11/6/200611/7/200611/7/2006 10:48:57 AMAPASS
Fire sprinkler work passed final inspection.
FIR06-00375 INSP-Final Inspection11/6/200611/7/200611/7/2006 10:48:07 AMAPASS
Required corrections have been completed, missing outside bell sign installed while on site, shell sprinkler work passed final inspection.
FIR06-00690 INSP-Final Inspection11/6/200611/7/200611/7/2006 10:45:59 AMAPASS
Per inspection done previously by S. Rogers, the fire alarm work passed field inspection, permit finaled.
FIR06-00507 INSP-Final Inspection11/6/200611/7/200611/7/2006 10:43:20 AMAPASS
Final shell fire alarm inspeciton passed, permit finaled.