FIR06-00687
| INSP-Final Inspection | 11/6/2006 | 11/7/2006 | 11/13/2006 1:17:57 PM | A | PASS |
|
|
Fire sprinkler permit finaled.
|
MIS06-00287
| FIR-Final | 11/6/2006 | 11/7/2006 | 11/8/2006 8:31:54 AM | A | CANC |
|
|
No time available to complete this inspection today.
|
FIR06-00065
| INSP-Final Inspection | 11/6/2006 | 11/7/2006 | 11/7/2006 3:51:20 PM | P | PART |
|
|
Items from previous inspection verified for completion, forward flow completed, okay for final when ball drip and FDC caps are installed.
|
FIR06-00836
| INSP-Sprinkler Rough-in | 11/7/2006 | 11/7/2006 | 11/7/2006 3:45:25 PM | P | PART |
|
|
OH rough-in is acceptable.
|
BLD05-03029
| BLD-Final | 11/7/2006 | 11/7/2006 | 11/7/2006 3:44:22 PM | P | FAIL |
|
|
SD within 20' of a cooking appliance must be "push to silence" or of the photoelectric type, SD must not be located within 3' of an adjacent opening to a room containing a shower, detectors at two locations need the dust covers removed before final.
|
BLD05-03335
| FIRE-Final Inspection | 11/7/2006 | 11/7/2006 | 11/7/2006 2:31:43 PM | P | FAIL |
|
|
The project related fire sprinkler permit must be approved and finaled prior to building life safety final.
|
BLD05-03029
| FIRE-Final Inspection | 11/6/2006 | 11/7/2006 | 11/7/2006 2:30:14 PM | P | DEFR |
|
|
|
FIR06-00807
| INSP-Sprinkler Rough-in | 11/7/2006 | 11/7/2006 | 11/7/2006 2:26:58 PM | P | PART |
|
|
Overhead rough-in is acceptabe pending verification the original system design can support up to three heads off 1" pipe as newly installed at one loction in the front canopy area.
|
FIR06-00137
| INSP-Final Inspection | 11/7/2006 | 11/7/2006 | 11/7/2006 2:21:56 PM | P | PASS |
|
|
Inspected resubmittals, verified UG supply is approved for the 4" size installed, c/n items have been amended, noted to contractor to provide signage at the door to the riser room.
|
FIR06-00672
| INSP-Sprinkler Rough-in | 11/7/2006 | 11/7/2006 | 11/7/2006 2:05:22 PM | P | PART |
|
|
Inspection for a portion of the drop ceiling areas at the main seating area and the kitchen prep. hallway are okay for cover, several pendent heads at scattered locations are not yet installed.
|
BLD06-01798
| FIRE-Final Inspection | 11/6/2006 | 11/7/2006 | 11/7/2006 2:01:27 PM | A | PASS |
|
|
Items on c/n have been completed, fire life safety inspection passed.
|
FIR06-00855
| INSP-Final Inspection | 11/6/2006 | 11/7/2006 | 11/7/2006 2:00:37 PM | A | PASS |
|
|
Fire sprinkler work completed satisfactory, permit finaled.
|
FIR06-00808
| INSP-Sprinkler Rough-in | 11/7/2006 | 11/7/2006 | 11/7/2006 12:56:54 PM | P | PART |
|
|
OH rough-in at the drop ceiling areas only are good for cover.
|
BLD06-00769
| FIRE-Final Inspection | 11/6/2006 | 11/7/2006 | 11/7/2006 12:55:39 PM | A | PART |
|
|
Required corrections for unit 315 second floor have been verified for completion.
|
BLD06-01492
| FIRE-Final Inspection | 11/7/2006 | 11/7/2006 | 11/7/2006 11:15:07 AM | A | PASS |
|
|
Fire life safety is acceptable.
|
FIR06-00588
| INSP-Final Inspection | 11/7/2006 | 11/7/2006 | 11/7/2006 11:14:34 AM | P | PASS |
|
|
Fire sprinkler permit finaled.
|
FIR06-00072
| FIR-Aging Inspection | 11/7/2006 | 11/7/2006 | 11/7/2006 10:55:27 AM | | DONE |
|
|
Scope of work as described has been completed by a different contractor.
|
FIR06-00712
| INSP-Final Inspection | 11/6/2006 | 11/7/2006 | 11/7/2006 10:50:52 AM | A | PASS |
|
|
One missing escutcheon installed while on site, fire sprinkler work completed satisfactory, permit finaled.
|
FIR06-00695
| INSP-Final Inspection | 11/6/2006 | 11/7/2006 | 11/7/2006 10:49:57 AM | A | PASS |
|
|
Fire sprinkler passed inspection, permit finaled.
|
FIR06-00694
| INSP-Final Inspection | 11/6/2006 | 11/7/2006 | 11/7/2006 10:48:57 AM | A | PASS |
|
|
Fire sprinkler work passed final inspection.
|
FIR06-00375
| INSP-Final Inspection | 11/6/2006 | 11/7/2006 | 11/7/2006 10:48:07 AM | A | PASS |
|
|
Required corrections have been completed, missing outside bell sign installed while on site, shell sprinkler work passed final inspection.
|
FIR06-00690
| INSP-Final Inspection | 11/6/2006 | 11/7/2006 | 11/7/2006 10:45:59 AM | A | PASS |
|
|
Per inspection done previously by S. Rogers, the fire alarm work passed field inspection, permit finaled.
|
FIR06-00507
| INSP-Final Inspection | 11/6/2006 | 11/7/2006 | 11/7/2006 10:43:20 AM | A | PASS |
|
|
Final shell fire alarm inspeciton passed, permit finaled.
|