Inspections for the day of: Wednesday, November 7, 2007.
Number of inspections: 15
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR06-00584 INSP-Final Inspection11/6/200711/7/200711/8/2007 2:30:32 PMAPART
Final pending ceiling tile and escutcheons, noted items from the previous inspection are complete.
FIR07-00749 INSP-Alarm Testing11/5/200711/7/200711/8/2007 2:25:51 PMAPART
Fire alarm work passed field inspection, final pending approved manual pull station locations within the remodeled area.
FIR07-00531 INSP-Final Inspection11/5/200711/7/200711/7/2007 4:32:18 PMPPASS
OH hydrostatic testing completed satisfactory, installation is acceptable, noted flexible couplings need to be added at the relocated hose station supply pipes per NFPA 13-see review comments, agreed to verify completion at the life safety final. Fire sprinkler permit finaled.
FIR07-00222 INSP-Final Inspection11/6/200711/7/200711/7/2007 4:28:08 PMAFAIL
Field installation does not match approved plan documents.
FIR07-00768 INSP-Sprinkler Rough-in/Hydro11/7/200711/7/200711/7/2007 4:23:21 PMPPART
Conference to discuss fire sprinkler head locations as field installed.
FIR07-00420 INSP-Final Inspection11/7/200711/7/200711/7/2007 1:47:10 PMPPASS
Fire sprinkler permit finaled.
FIR07-00420 INSP-Sprinkler Rough-in/Hydro11/6/200711/7/200711/7/2007 1:46:18 PMPPART
Hydrostatic testing of the preaction system piping completed per K. Roule.
BLD07-00986 FIRE-Final Inspection11/5/200711/7/200711/7/2007 1:42:09 PMAPASS
Access gates approved per FD, door hardware at the main entry/exit installed while on site, life safety inspection completed acceptable per site visit by K. Roule.
FIR07-00106 INSP-Sprinkler Rough-in/Hydro11/6/200711/7/200711/7/2007 1:39:54 PMAPART
UG fire supply line hydrostatic test passed.
FIR07-00502 INSP-Sprinkler Rough-in/Hydro11/6/200711/7/200711/7/2007 1:39:08 PMAPART
OH hydrostatic test passed, c/n items from the previous inspection have been completed, noted that no provision has been made at the riser for forward flow testing of the DCVA backflow.
FIR07-00413 FIR-Aging Inspection11/7/200711/7/200711/7/2007 10:53:25 AM DEFR
Under construction.
FIR07-00412 FIR-Aging Inspection11/7/200711/7/200711/7/2007 10:52:34 AM DEFR
Under construction.
BLD07-02244 FIRE-Final Inspection11/2/200711/7/200711/7/2007 10:50:15 AMAPART
Fire life safety pending satisfactory fire alarm testing.
FIR06-00595 INSP-Alarm Testing11/5/200711/7/200711/7/2007 10:48:36 AMAFAIL
FA inspection for the 3rd floor NE quad failed due to strobe synchronization issues.
FIR07-00755 INSP-Sprinkler Rough-in/Hydro11/7/200711/7/200711/7/2007 12:00:00 AMPCANC