ELE08-02957
| Permanent Service | 11/7/2008 | 11/7/2008 | 11/7/2008 3:41:27 PM | P | PASS |
|
|
cal Phone #: ###-#### p/s o/h new ok
|
ELE08-02086
| Final | 11/7/2008 | 11/7/2008 | 11/7/2008 2:49:50 PM | P | FAIL |
|
|
Phone #: ###-#### Internet Inspection Request from: Sean Peltier box fill and protect cables in island cabinet, needs clearence for subpanel remove window seat called corr posted
|
ELE08-02983
| Electrical Rough-In | 11/7/2008 | 11/7/2008 | 11/7/2008 1:42:29 PM | P | PART |
|
|
TED CALL PRIOR TO HEADING TO SITE. MEAT CASE UNDERGROUND. Phone #: ###-#### Internet Inspection Request from: Sean DeLacy ok
|
ELE08-02736
| Final | 11/7/2008 | 11/7/2008 | 11/7/2008 12:57:35 PM | P | FAIL |
|
|
Phone #: ###-#### Internet Inspection Request from: Celinda Winters called corr posted 410.62(C) shall not use cord for fixed wiring of fixtures, or install as code noted states, upstairs room 422.31 needs lockout clip for W H breaker
|
ELE08-02671
| Final | 11/6/2008 | 11/7/2008 | 11/7/2008 10:16:11 AM | A | FAIL |
|
|
JEROD Phone #: ###-#### corr 210.52(C) needs recept right of sink for countertop space 2ft 4ft rule, 410.2&16 clearence MB closet fixture, 250.148 grd box kit. island, 210.11 (C) (2) outside recpt not allowed on laundry circuit this is the second time I've told contr, needs permit for hot tub , and shall wire hot tub to meet art 680
|
ELE08-02645
| Final | 11/6/2008 | 11/7/2008 | 11/7/2008 9:28:02 AM | A | PASS |
|
|
jeff Phone #: ###-#### survey needs gfci for both refer recepts called final ok no card
|
ELE08-02897
| Electrical Rough-In | 11/6/2008 | 11/7/2008 | 11/7/2008 8:51:26 AM | A | PASS |
|
|
patrick Phone #: ###-#### outside light box shall be flush with siding, owner will fix, at time of final check for main breaker in panel, manufacture's instructions r/i ok
|
ELE08-02873
| Electrical Rough-In | 11/6/2008 | 11/7/2008 | 11/7/2008 8:09:04 AM | A | PART |
|
|
eric Phone #: ###-#### u/g inside ok
|