Inspections for the day of: Monday, November 7, 2011.
Number of inspections: 18
Percentage of inspections complete: 94 %
Percentage of inspections not complete: 6 %
Contact Information
InspectorDaryl DeGrange
TitleELE-INSPECTION SUPV
Phone #794-1379
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE11-02509 Permanent Service11/7/201111/7/201111/7/2011 2:01:46 PMPFAIL
There hasn''t been a meter at this location for over a year, Idaho Power is requiring an inspection of the service before powering.
Access code is 9771, thanks. Phone #: ###-#### >> Inspection requested via web by Stephen Kren Service grounding requires 2 eight foot ground rods six feet apart unless proven 25 ohms or less of resistance. Rerun grounding conductor through non-conductive connector. Connect water pipe bond within first five feet where water pipe enters. Finish labeling panel circuitry after power has been reinstated
ELE11-02428 Final11/7/201111/7/201111/7/2011 1:19:48 PMPPASS
this is a final on bathroom and additional final on new circuits and exit signs Phone #: ###-#### >> Inspection requested via web by Paul Klindt final ok
ELE11-01338 Final11/7/201111/7/201111/7/2011 12:30:57 PMPPASS
>> Inspection requested via web by Clint Tate final ok
ELE11-02502 Electrical Rough-In11/4/201111/7/201111/7/2011 12:30:31 PMAPASS
Contact: Cary Sims - Late AM or early PM underground inspection please. Pouring concrete at 3:00 PM Phone #: ###-#### >> Inspection requested via web by Deb Gooden rough-in ok pour concrete
ELE11-01338 Electrical Rough-In11/7/201111/7/201111/7/2011 11:42:46 AMPPASS
8/31/2011 Rough-in ok ceiling grid
ELE11-01338 Electrical Rough-In11/7/201111/7/201111/7/2011 11:42:26 AMPPASS
8/23/2011 Rough-in ok cover outside perimeter walls
ELE11-00659 ELE-Aging Inspection11/7/201111/7/201111/7/2011 9:53:56 AM DONE
see final
ELE11-00659 Final11/7/201111/7/201111/7/2011 9:48:58 AMPPASS
Mike Phone #: ###-#### final ok
ELE11-00766 ELE-Aging Inspection11/7/201111/7/201111/7/2011 9:47:23 AM DONE
see final
ELE11-00766 Final11/7/201111/7/201111/7/2011 9:46:01 AMPPASS
final ok
ELE11-00090 Final11/7/201111/7/201111/7/2011 9:29:49 AMAPASS
final ok sign no longer there
ELE11-00632 ELE-Aging Inspection11/7/201111/7/201111/7/2011 9:16:10 AM DONE
see final
ELE11-00632 Final11/7/201111/7/201111/7/2011 9:15:15 AMAPASS
final ok 2- UL listed wall mount signs
ELE11-00726 Final11/7/201111/7/201111/7/2011 8:35:02 AMAPASS
Final ok UL listed sign
ELE11-01978 Final11/7/201111/7/201111/7/2011 8:28:47 AMAPASS
Phone #: ###-#### >> Inspection requested via web by Ron Zimmerman final ok
ELE10-02400 ELE-Aging Inspection11/7/201111/7/201111/7/2011 6:20:04 AM DONE
still under construction
ELE11-02013 Permanent Service11/7/201111/7/201111/7/2011 12:00:00 AMPCANC
tom Phone #: ###-####
ESC11-00804 Site Preparation11/7/201111/7/2011