ELE11-01990
| ELE-Aging Inspection | 11/7/2012 | 11/7/2012 | 11/13/2012 3:15:03 PM | | DONE |
|
|
called contractor. Believe this was service change that did not get finalled.
|
ELE09-00849
| ELE-Aging Inspection | 11/7/2012 | 11/7/2012 | 11/9/2012 3:39:43 PM | | PASS |
|
|
Finalled under permit pulled 2011. scope of work covered under that permit
|
ELE11-02806
| Electrical Rough-In | 11/6/2012 | 11/7/2012 | 11/8/2012 7:53:57 AM | A | FAIL |
|
|
Please call Mike 30 min. prior at ###-####. Ceiling inspection. Phone #: ###-#### >> Inspection requested via web by Shawna Gates Existing wiring in need of repair. 1. 314.17 (B) Metal boxes for HVAC shall have insulating bushing where conductors enter. 2. 314.23 (D)2 Boxes shall be supported by support wires at both ends HVAC. 3. 314.25 All j-boxes shall have covers.4. 110.12 (A) Unused openings in boxes shall be closed. 5. 300.11 Cables and raceways shall not be supported by ceiling grid. 6. 800.100(D) A cable tray is considered an equiptment grounding conductor. A #6 minimum insulated grounding conductor shall be installed between cable tray and building grounding system. 7. 330.30 (B) MC cable shall be supported with in 12 " of every box or fitting.
|
ELE12-02743
| Rough-In Permanent Service | 11/7/2012 | 11/7/2012 | 11/7/2012 2:17:51 PM | P | PASS |
|
|
Phone #: ###-#### >> Inspection requested via web by Dan Rohl Rough in ok cover p/s u/g n ok
|
GCE12-00167
| GCE-Rough-In Permanent Service | 11/7/2012 | 11/7/2012 | 11/7/2012 1:45:32 PM | P | PASS |
|
|
Ed @ ###-#### Rough in ok cover p/s u/g n ok
|
ELE11-02692
| Final | 11/7/2012 | 11/7/2012 | 11/7/2012 1:37:27 PM | P | PASS |
|
|
Contact: Garrett Collins, Please call 30 minutes before going Phone #: ###-#### >> Inspection requested via web by Deb Gooden Shell Final ok
|
ELE12-01638
| Final | 11/7/2012 | 11/7/2012 | 11/7/2012 1:31:15 PM | P | PASS |
|
|
Steve. Phone #: ###-#### >> Inspection requested via web by Sean DeLacy 2000 amp main load test completed by Current Technologies Job # 2012266 Passed Final ok
|
ELE12-02740
| Temporary Service | 11/7/2012 | 11/7/2012 | 11/7/2012 11:09:39 AM | P | PASS |
|
|
Mucho Phone #: ###-#### t/s u/g n ok
|
ELE12-02742
| Temporary Service | 11/7/2012 | 11/7/2012 | 11/7/2012 10:48:36 AM | P | PASS |
|
|
Phone #: ###-#### >> Inspection requested via web by Dan Rohl t/s u/g n ok
|
ELE12-01489
| Final | 11/6/2012 | 11/7/2012 | 11/7/2012 10:26:29 AM | A | PASS |
|
|
Tom Phone #: ###-#### final ok
|
ELE12-02029
| Final | 11/7/2012 | 11/7/2012 | 11/7/2012 10:09:23 AM | A | PASS |
|
|
Hello, could you please call ahead so I can meet you down there to let you in. Thanks, Mark Phone #: ###-#### >> Inspection requested via web by Mark Hennequin Final ok
|
ELE12-02736
| Permanent Service | 11/6/2012 | 11/7/2012 | 11/7/2012 8:53:40 AM | A | CANC |
|
|
Phone #: ###-#### >> Inspection requested via web by Neal Rumsey needed temp service
|
ELE12-02736
| Temporary Service | 11/7/2012 | 11/7/2012 | 11/7/2012 8:52:26 AM | P | PASS |
|
|
Phone #: ###-#### >> Inspection requested via web by Neal Rumsey t/s u/g n ok
|
ELE12-02727
| Temporary Service | 11/6/2012 | 11/7/2012 | 11/7/2012 8:45:33 AM | A | PASS |
|
|
THANKS Phone #: ###-#### >> Inspection requested via web by Bob Glenn t/s u/g n ok
|
ELE12-02732
| Temporary Service | 11/6/2012 | 11/7/2012 | 11/7/2012 8:26:55 AM | A | PASS |
|
|
THANKS Phone #: ###-#### >> Inspection requested via web by Bob Glenn t/s u/g n ok
|
ELE12-02705
| Conference | 11/5/2012 | 11/7/2012 | 11/6/2012 4:33:38 PM | A | DONE |
|
|
Storm drain inlet protection; Phone #: ###-####
|
ELE12-02715
| Temporary Service | 11/5/2012 | 11/7/2012 | 11/6/2012 8:08:59 AM | A | CANC |
|
|
THANK YOU Phone #: ###-#### >> Inspection requested via web by Bob Glenn Inspection cancelled from web by: Bob Glenn
|