Inspections for the day of: Wednesday, November 7, 2012.
Number of inspections: 17
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRock A. Hudson
TitleELE-INSPECTOR
Phone #794-6794
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE11-01990 ELE-Aging Inspection11/7/201211/7/201211/13/2012 3:15:03 PM DONE
called contractor. Believe this was service change that did not get finalled.
ELE09-00849 ELE-Aging Inspection11/7/201211/7/201211/9/2012 3:39:43 PM PASS
Finalled under permit pulled 2011. scope of work covered under that permit
ELE11-02806 Electrical Rough-In11/6/201211/7/201211/8/2012 7:53:57 AMAFAIL
Please call Mike 30 min. prior at ###-####. Ceiling inspection. Phone #: ###-#### >> Inspection requested via web by Shawna Gates Existing wiring in need of repair. 1. 314.17 (B) Metal boxes for HVAC shall have insulating bushing where conductors enter. 2. 314.23 (D)2 Boxes shall be supported by support wires at both ends HVAC. 3. 314.25 All j-boxes shall have covers.4. 110.12 (A) Unused openings in boxes shall be closed. 5. 300.11 Cables and raceways shall not be supported by ceiling grid. 6. 800.100(D) A cable tray is considered an equiptment grounding conductor. A #6 minimum insulated grounding conductor shall be installed between cable tray and building grounding system. 7. 330.30 (B) MC cable shall be supported with in 12 " of every box or fitting.
ELE12-02743 Rough-In Permanent Service11/7/201211/7/201211/7/2012 2:17:51 PMPPASS
Phone #: ###-#### >> Inspection requested via web by Dan Rohl Rough in ok cover p/s u/g n ok
GCE12-00167 GCE-Rough-In Permanent Service11/7/201211/7/201211/7/2012 1:45:32 PMPPASS
Ed @ ###-#### Rough in ok cover p/s u/g n ok
ELE11-02692 Final11/7/201211/7/201211/7/2012 1:37:27 PMPPASS
Contact: Garrett Collins, Please call 30 minutes before going Phone #: ###-#### >> Inspection requested via web by Deb Gooden Shell Final ok
ELE12-01638 Final11/7/201211/7/201211/7/2012 1:31:15 PMPPASS
Steve. Phone #: ###-#### >> Inspection requested via web by Sean DeLacy 2000 amp main load test completed by Current Technologies Job # 2012266 Passed Final ok
ELE12-02740 Temporary Service11/7/201211/7/201211/7/2012 11:09:39 AMPPASS
Mucho Phone #: ###-#### t/s u/g n ok
ELE12-02742 Temporary Service11/7/201211/7/201211/7/2012 10:48:36 AMPPASS
Phone #: ###-#### >> Inspection requested via web by Dan Rohl t/s u/g n ok
ELE12-01489 Final11/6/201211/7/201211/7/2012 10:26:29 AMAPASS
Tom Phone #: ###-#### final ok
ELE12-02029 Final11/7/201211/7/201211/7/2012 10:09:23 AMAPASS
Hello, could you please call ahead so I can meet you down there to let you in.
Thanks, Mark Phone #: ###-#### >> Inspection requested via web by Mark Hennequin Final ok
ELE12-02736 Permanent Service11/6/201211/7/201211/7/2012 8:53:40 AMACANC
Phone #: ###-#### >> Inspection requested via web by Neal Rumsey needed temp service
ELE12-02736 Temporary Service11/7/201211/7/201211/7/2012 8:52:26 AMPPASS
Phone #: ###-#### >> Inspection requested via web by Neal Rumsey t/s u/g n ok
ELE12-02727 Temporary Service11/6/201211/7/201211/7/2012 8:45:33 AMAPASS
THANKS Phone #: ###-#### >> Inspection requested via web by Bob Glenn t/s u/g n ok
ELE12-02732 Temporary Service11/6/201211/7/201211/7/2012 8:26:55 AMAPASS
THANKS Phone #: ###-#### >> Inspection requested via web by Bob Glenn t/s u/g n ok
ELE12-02705 Conference11/5/201211/7/201211/6/2012 4:33:38 PMADONE
Storm drain inlet protection; Phone #: ###-####
ELE12-02715 Temporary Service11/5/201211/7/201211/6/2012 8:08:59 AMACANC
THANK YOU Phone #: ###-#### >> Inspection requested via web by Bob Glenn Inspection cancelled from web by: Bob Glenn