ELE12-02320
| Final | 11/7/2012 | 11/7/2012 | 11/8/2012 2:28:20 PM | P | FAIL |
|
|
We have proper key for entrance to the property Phone #: ###-#### >> Inspection requested via web by John McConnell talked wth installer, said response would be on-line, gave 447 phone number, NEC 110.26(A) shall provide work space about equipment,408.36(D) shall supply additional fastener for back fed devices, 230.66 shall use equipment marked as service equipment, 250.50 all grounding electrodes shall be bonded together to form grounding electrode system, 110.22 shall provide disconnect identification, 690.17 shall provide labelling terminals can be energized from other source, 230, shall group and label disconnects, 110 combiner shall be listed assembly
|
ELE12-01587
| Electrical Rough-In | 11/7/2012 | 11/7/2012 | 11/7/2012 2:28:10 PM | P | PASS |
|
|
Joann Phone #: ###-#### ri ok
|
ELE11-02855
| Electrical Rough-In | 11/7/2012 | 11/7/2012 | 11/7/2012 12:41:48 PM | P | PASS |
|
|
ug for light bases//Steve Phone #: ###-#### bases ok
|
ELE12-02685
| Electrical Rough-In | 11/6/2012 | 11/7/2012 | 11/7/2012 11:54:54 AM | P | NR |
|
|
underground work for a concrete pad. Please call Darin prior to arrival @ ###-#### Phone #: ###-#### >> Inspection requested via web by Rhonda Zamagni called, contractor wants am for 11-8-12
|
ELE12-02489
| Electrical Rough-In | 11/7/2012 | 11/7/2012 | 11/7/2012 11:17:36 AM | A | PASS |
|
|
grid ceiling Phone #: ###-#### >> Inspection requested via web by Lee VanSchoiack ok cover ceiling only
|
ELE12-02716
| Rough-In Permanent Service | 11/6/2012 | 11/7/2012 | 11/7/2012 10:49:09 AM | A | PASS |
|
|
thanks, Bill ? ###-#### Phone #: ###-#### >> Inspection requested via web by Bob Glenn ri ok, p/s u/g n ok
|
ELE12-02550
| Conference | 11/6/2012 | 11/7/2012 | 11/7/2012 10:02:35 AM | A | DONE |
|
|
Meet at 17C lobby to discuss UL listing on LED lighting fixtures. Phone #: ###-#### >> Inspection requested via web by Paul Cook talked about special fixtures for building installations, listings for fixtures marketed
|
ELE12-01587
| Electrical Rough-In | 11/5/2012 | 11/7/2012 | 11/7/2012 8:58:03 AM | A | FAIL |
|
|
Joann Phone #: ###-#### met owner, shall staple nm within 8" of box, re-pull wire with split jacket, check box fill, finish make-up, staple over panel, abandon old boxes
|
ELE12-02701
| Electrical Rough-In | 11/6/2012 | 11/7/2012 | 11/7/2012 8:37:55 AM | A | PASS |
|
|
The key is on top of the meter base at the back of the house. Thank You. Phone #: ###-#### >> Inspection requested via web by Clay Morgan ri ok
|
ELE12-02733
| Permanent Service | 11/6/2012 | 11/7/2012 | 11/7/2012 7:56:19 AM | A | PASS |
|
|
Power off over a year, need inspection on service to get power on. House is vacant, everthing on outside. Any questions call Andy @ ###-#### Phone #: ###-#### >> Inspection requested via web by Andy Rose p/s o/h rec ok
|