Inspections for the day of: Wednesday, November 7, 2012.
Number of inspections: 10
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorBob Reichert
TitleELE-INSPECTOR
Phone #794-1923
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE12-02320 Final11/7/201211/7/201211/8/2012 2:28:20 PMPFAIL
We have proper key for entrance to the property Phone #: ###-#### >> Inspection requested via web by John McConnell talked wth installer, said response would be on-line, gave 447 phone number, NEC 110.26(A) shall provide work space about equipment,408.36(D) shall supply additional fastener for back fed devices, 230.66 shall use equipment marked as service equipment, 250.50 all grounding electrodes shall be bonded together to form grounding electrode system, 110.22 shall provide disconnect identification, 690.17 shall provide labelling terminals can be energized from other source, 230, shall group and label disconnects, 110 combiner shall be listed assembly
ELE12-01587 Electrical Rough-In11/7/201211/7/201211/7/2012 2:28:10 PMPPASS
Joann Phone #: ###-#### ri ok
ELE11-02855 Electrical Rough-In11/7/201211/7/201211/7/2012 12:41:48 PMPPASS
ug for light bases//Steve Phone #: ###-#### bases ok
ELE12-02685 Electrical Rough-In11/6/201211/7/201211/7/2012 11:54:54 AMPNR
underground work for a concrete pad. Please call Darin prior to arrival @ ###-#### Phone #: ###-#### >> Inspection requested via web by Rhonda Zamagni called, contractor wants am for 11-8-12
ELE12-02489 Electrical Rough-In11/7/201211/7/201211/7/2012 11:17:36 AMAPASS
grid ceiling Phone #: ###-#### >> Inspection requested via web by Lee VanSchoiack ok cover ceiling only
ELE12-02716 Rough-In Permanent Service11/6/201211/7/201211/7/2012 10:49:09 AMAPASS
thanks, Bill ? ###-#### Phone #: ###-#### >> Inspection requested via web by Bob Glenn ri ok, p/s u/g n ok
ELE12-02550 Conference11/6/201211/7/201211/7/2012 10:02:35 AMADONE
Meet at 17C lobby to discuss UL listing on LED lighting fixtures. Phone #: ###-#### >> Inspection requested via web by Paul Cook talked about special fixtures for building installations, listings for fixtures marketed
ELE12-01587 Electrical Rough-In11/5/201211/7/201211/7/2012 8:58:03 AMAFAIL
Joann Phone #: ###-#### met owner, shall staple nm within 8" of box, re-pull wire with split jacket, check box fill, finish make-up, staple over panel, abandon old boxes
ELE12-02701 Electrical Rough-In11/6/201211/7/201211/7/2012 8:37:55 AMAPASS
The key is on top of the meter base at the back of the house. Thank You. Phone #: ###-#### >> Inspection requested via web by Clay Morgan ri ok
ELE12-02733 Permanent Service11/6/201211/7/201211/7/2012 7:56:19 AMAPASS
Power off over a year, need inspection on service to get power on. House is vacant, everthing on outside. Any questions call Andy @ ###-#### Phone #: ###-#### >> Inspection requested via web by Andy Rose p/s o/h rec ok