Inspections for the day of: Monday, November 7, 2016.
Number of inspections: 3
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorKatie Marron
TitleFIRE INSPECTOR
Phone #395-7809
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR16-00569 INSP-Sprinkler Rough-in11/7/201611/7/201611/7/2016 4:04:15 PMPCANC
Contact number provided was a discontinued number. Reschedule and provide correct contact information.
BLD16-02781 FIRE-Final Inspection11/7/201611/7/201611/7/2016 2:56:07 PMPFAIL
Upright Sprinkler heads were painted. Additional coverage needs to be added to the restroom do to the dropped/hardlid ceiling. The entire space needs to be reviewed by a licensed sprinkler contractor to determine if additional modifications due to the walls are required. A sprinkler permit is required.
BLD16-02720 FIRE-Conference11/7/201611/7/201611/7/2016 12:00:00 AMPDONE
Discussed with architect on address number placement. Directed that if building numbers were not visible from the street than additional signage at the street/gate would be required.