Inspections for the day of: Tuesday, November 7, 2017.
Number of inspections: 7
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJim Page
TitleFIRE INSPECTOR
Phone #208-914-5431
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD17-02710 FIRE-Final Inspection11/6/201711/7/201711/7/2017 4:07:22 PMPFAIL
Doors with mag locks need to release under general fire alarm. Ceiling tiles need to be in place for fire sprinkler heat collection. Fire alarm permit needs to be in finaled status for life fire safety inspection to be completed.
FIR17-00047 INSP-Sprinkler Rough-in/Hydro11/7/201711/7/201711/7/2017 11:29:55 AMPPART
Rough in inspection complete for overhead fire sprinkler, overhead fire sprinkler piping located between conditioned spaces approved for cover, piping located in attic spaces cannot be covered until tenting inspection is completed and passed.
FIR17-00047 INSP-Final Inspection11/7/201711/7/201711/7/2017 11:27:53 AMACANC
Wrong inspection request entered, this request is cancelled.
FIR17-00473 INSP-Final Inspection11/6/201711/7/201711/7/2017 10:45:33 AMAPASS
Final fire sprinkler inspection passed/complete.
FIR17-00591 INSP-Final Inspection11/6/201711/7/201711/7/2017 10:18:30 AMAFAIL
Mag locks on the east and west exterior doors need to interface with the fire alarm panel, mag locks need to release under general fire alarm. Ceiling mounted audio/visual devices located in the level 1 locker/shower rooms need to be changed to a weather proof device.
BLD16-04280 FIRE-Final Inspection11/6/201711/7/201711/7/2017 9:05:25 AMAPASS
Exit signs are in place, final life fire safety inspection passed/complete.
BLD17-02655 FIRE-Final Inspection11/6/201711/7/201711/7/2017 8:26:23 AMAPASS
Previously noted items have been repaired. Fire sprinkler inspection is complete, no fire alarm modifications, fire extinguishers are in place with current inspection tags. Final life fire safety inspection passed/complete.