BLD17-02710
| FIRE-Final Inspection | 11/6/2017 | 11/7/2017 | 11/7/2017 4:07:22 PM | P | FAIL |
|
|
Doors with mag locks need to release under general fire alarm. Ceiling tiles need to be in place for fire sprinkler heat collection. Fire alarm permit needs to be in finaled status for life fire safety inspection to be completed.
|
FIR17-00047
| INSP-Sprinkler Rough-in/Hydro | 11/7/2017 | 11/7/2017 | 11/7/2017 11:29:55 AM | P | PART |
|
|
Rough in inspection complete for overhead fire sprinkler, overhead fire sprinkler piping located between conditioned spaces approved for cover, piping located in attic spaces cannot be covered until tenting inspection is completed and passed.
|
FIR17-00047
| INSP-Final Inspection | 11/7/2017 | 11/7/2017 | 11/7/2017 11:27:53 AM | A | CANC |
|
|
Wrong inspection request entered, this request is cancelled.
|
FIR17-00473
| INSP-Final Inspection | 11/6/2017 | 11/7/2017 | 11/7/2017 10:45:33 AM | A | PASS |
|
|
Final fire sprinkler inspection passed/complete.
|
FIR17-00591
| INSP-Final Inspection | 11/6/2017 | 11/7/2017 | 11/7/2017 10:18:30 AM | A | FAIL |
|
|
Mag locks on the east and west exterior doors need to interface with the fire alarm panel, mag locks need to release under general fire alarm. Ceiling mounted audio/visual devices located in the level 1 locker/shower rooms need to be changed to a weather proof device.
|
BLD16-04280
| FIRE-Final Inspection | 11/6/2017 | 11/7/2017 | 11/7/2017 9:05:25 AM | A | PASS |
|
|
Exit signs are in place, final life fire safety inspection passed/complete.
|
BLD17-02655
| FIRE-Final Inspection | 11/6/2017 | 11/7/2017 | 11/7/2017 8:26:23 AM | A | PASS |
|
|
Previously noted items have been repaired. Fire sprinkler inspection is complete, no fire alarm modifications, fire extinguishers are in place with current inspection tags. Final life fire safety inspection passed/complete.
|