Inspections for the day of: Wednesday, November 7, 2018.
Number of inspections: 8
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRock A. Hudson
TitleELE-INSPECTOR
Phone #794-6794
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE14-01093 ELE-Aging Inspection11/7/201811/7/201811/15/2018 2:31:29 PM PASS
Called owner and asked if still under construction, he replied work should be finished by end of next year.
ELE18-04305 Electrical Rough-In11/7/201811/7/201811/7/2018 3:44:59 PMPPASS
Cover inspection in new walls Phone #: ###-#### Inspection requested via web by Steve Craig
As per Daryl DeGrange existing service ok to remain as originally installed, CT meter on exterior with overhead service entrance conductors passing unfused through roof to 2 main breaker panels.
250.24- Grounded electrical systems shall have a grounding electrode system installed as described in 250.52.
Wall rough in ok cover.
ELE18-02828 Final11/7/201811/7/201811/7/2018 2:40:04 PMPPASS
Sliding glass door on side of the house should be open. Please call if you need access. Phone #: ###-#### Inspection requested via web by Nick Larson Final ok
ELE18-03060 Final11/7/201811/7/201811/7/2018 11:35:00 AMAFAIL
GARAGE CODE 4224 Phone #: ###-#### Inspection requested via web by Bob Glenn 300.15- All NM cables shall terminate in a box. Level 1 TV location wire stubbed back in wall. Need a box and cover.
ELE18-03140 Final11/6/201811/7/201811/7/2018 10:40:04 AMAFAIL
garage code 2524 Phone #: ###-#### Inspection requested via web by Darryn Coburn 110.3- All devices shall be working. Level 1 bedroom receptacle to left of window not working. 314.25- All boxes shall have covers. Level 1 bedroom buried box right of window.
ELE18-03249 Final11/6/201811/7/201811/7/2018 10:30:54 AMAFAIL
garage code 2324 Phone #: ###-#### Inspection requested via web by Darryn Coburn BCC 4 05 24(D)- Electrical inspector shall have access to all areas where work has been performed. Carpet being installed, door removed and stacked up in bathrooms. Garage doors and 4x8 sheets blocking receptacles.
ELE18-03052 Final11/6/201811/7/201811/7/2018 10:28:14 AMAPASS
garage code 2624 Phone #: ###-#### Inspection requested via web by Darryn Coburn Final ok
ELE18-03802 Electrical Rough-In11/7/201811/7/201811/7/2018 9:23:52 AMAPASS
Randy. Phone #: ###-#### Inspection requested via web by Sean DeLacy
Drop lids and north soffit rough in ok cover