Inspections for the day of: Thursday, November 7, 2019.
Number of inspections: 11
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRock A. Hudson
TitleELE-INSPECTOR
Phone #794-6794
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE19-01403 Electrical Rough-In11/7/201911/7/201911/7/2019 2:49:20 PMPFAIL
Contact John M. for level 2 pour #3 in slab raceways. Phone #: ###-#### Inspection requested via web by Tom Betty
300.18- Conduit runs shall be installed in complete runs.
352.30- PVC shall be supported at intervals not to exceed 3' for 1/2" thru 1" conduit.
Southeast and central east areas conduit installed and supported, about 1/2 of pour. Northeast and northern areas of pour conduit installation not complete at 2pm time of inspection. General contactor must give sufficient time to install raceways. Will recall for Friday AM, pour planned for 3:30pm.
ELE19-04117 Final11/7/201911/7/201911/7/2019 1:23:21 PMPPASS
Final electrical inspection in conjunction with Old Dominion final solar inspection.

Thank you ; have a great day! Phone #: ###-#### Inspection requested via web by JENNY EMEL
Final ok
ELE19-04263 Final11/7/201911/7/201911/7/2019 1:22:59 PMPPASS
I will meet you onsite. I have a key to get into the garage where the electric panel is. Phone #: ###-#### Inspection requested via web by Matt Oranday Final ok
ELE19-04306 Final11/6/201911/7/201911/7/2019 11:43:14 AMAPASS
Inspection request for hot tub hook up.
If no one is home please call and i will proved information for access. If there is any complications with access the general contractor will be about 20 minutes away Phone #: ###-#### Inspection requested via web by Keith Chetta Final ok
ELE19-04306 Electrical Rough-In11/7/201911/7/201911/7/2019 11:43:01 AMPPASS
Inspection request for hot tub hook up.
If no one is home please call and i will proved information for access. If there is any complications with access the general contractor will be about 20 minutes away Phone #: ###-#### Inspection requested via web by Keith Chetta
Exterior surface mounted with hsort underground. Rough in ok.
ELE19-04280 Electrical Rough-In11/6/201911/7/201911/7/2019 10:48:56 AMANH
call before i will meet you there. Phone #: ###-#### Inspection requested via web by Miles Berry
Called contact a 10:09 Arrived at 10:45, unit locked, no return call. Recall when accessible.
ELE19-04222 Temporary Service11/6/201911/7/201911/7/2019 10:36:26 AMAPASS
Phone #: ###-#### Inspection requested via web by Alan Lusk t/s u/g n ok
ELE19-04283 Temporary Service11/6/201911/7/201911/7/2019 10:25:15 AMAPASS
Phone #: ###-#### Inspection requested via web by Alan Lusk t/s u/g n ok
ELE19-04284 Temporary Service11/6/201911/7/201911/7/2019 10:07:10 AMAPASS
Phone #: ###-#### Inspection requested via web by Alan Lusk t/s u/g n ok
ELE19-04235 Rough-In Permanent Service11/6/201911/7/201911/7/2019 9:54:01 AMAPASS
Phone #: ###-#### Inspection requested via web by Alan Lusk
Rough in ok cover p/s u/g n ok
ELE19-02626 Final11/7/201911/7/201911/7/2019 9:07:26 AMAPASS
Contact Josh Slater
Thank you Phone #: ###-#### Inspection requested via web by Cathy Duchek Final ok