BLD19-04406
| FIRE-Final Inspection | 11/7/2019 | 11/7/2019 | 11/7/2019 1:57:06 PM | A | FAIL |
|
|
Provide annual inspection on fire extinguisher. Exit sign in place needs to be serviced or removed, exit light/emergency lighting was not operable at time of inspection.
|
BLD19-04379
| FIRE-Final Inspection | 11/7/2019 | 11/7/2019 | 11/7/2019 1:56:30 PM | P | FAIL |
|
|
Provide annual inspection on fire extinguisher. Exit sign in place needs to be serviced or removed, exit light/emergency lighting was not operable at time of inspection.
call to meet // Kyle Phone #: ###-####
|
BLD19-01578
| FIRE-Final Inspection | 11/6/2019 | 11/7/2019 | 11/7/2019 1:39:10 PM | P | PASS |
|
|
Previously noted items have been corrected, no fire sprinklers, no fire alarms, fire extinguisher is placed with a current inspection tag. Final life fire safety inspection is complete, sign off card not provided at time of inspection.
Call ahead to meet // Stacey Phone #: ###-####
|
BLD19-04424
| FIRE-Final Inspection | 11/7/2019 | 11/7/2019 | 11/7/2019 1:01:04 PM | P | PASS |
|
|
No fire sprinkler modifications, no fire alarm modifications, fire extinguishers are placed with current inspection tags. Final life fire safety inspection is complete, signatures provided on sign off card.
Larren Phone #: ###-####
|
BLD18-03657
| FIRE-Final Inspection | 11/7/2019 | 11/7/2019 | 11/7/2019 12:46:56 PM | P | PASS |
|
|
Fire sprinkler inspection is complete, fire alarm inspection for this area of work is complete (Fire alarm permit FIR19-00268 is for the entire building, permit will remain in issued status until fire alarm inspection for entire building is complete), fire extinguishers are placed with current inspection tags. Final life fire safety inspection for area of work complete.
Casey Phone #: ###-####
|
FIR19-00268
| INSP-Final Inspection | 11/7/2019 | 11/7/2019 | 11/7/2019 12:20:53 PM | P | PART |
|
|
Fire alarm inspection for surgical suite, southwest side of building complete to include corridors outside of surgical suite. Remaining areas to be inspected at a later date.
Phone #: ###-#### Inspection requested via web by Kristin Dolan
|
BLD19-04177
| FIRE-Final Inspection | 11/7/2019 | 11/7/2019 | 11/7/2019 11:17:47 AM | P | CANC |
|
|
Duplicate inspection request, this request is cancelled.
Kelly Phone #: ###-####
|
BLD19-04177
| FIRE-Final Inspection | 11/7/2019 | 11/7/2019 | 11/7/2019 11:17:11 AM | P | PASS |
|
|
Previously noted items have been corrected. Cooking appliances were removed for floor replacement, appliances must go back in original locations as discussed for proper hood suppression system coverage. No fire aalrm modifications, fire sprinkler inspection is complete, fire extinguishers are placed with current inspection tags. Final life fire safety inspection complete.
Kelly Phone #: ###-####
|
FIR19-00819
| INSP-Sprinkler Rough-in | 11/7/2019 | 11/7/2019 | 11/7/2019 11:15:01 AM | P | PART |
|
|
Rough to cover inspection for overhead fire sprinkler piping above hardlids complete, hardlids approved for cover.
Phone #: ###-#### Inspection requested via web by Sam Ball
|
BLD19-04406
| FIRE-Conference | 11/6/2019 | 11/7/2019 | 11/7/2019 10:32:09 AM | A | CANC |
|
|
Request was for a fire inspection, not a conference, this request is cancelled.
Konda Phone #: ###-####
|
FIR19-00521
| INSP-Sprinkler Rough-in/Hydro | 11/6/2019 | 11/7/2019 | 11/7/2019 10:08:30 AM | A | FAIL |
|
|
Install does not match city approved drawings, notated about 6 areas on the city approved drawings, inspection was stopped.
Call before heading out, thanks! Phone #: ###-#### Inspection requested via web by Anthony Minichiello
|
FIR19-00828
| INSP-Final Inspection | 11/6/2019 | 11/7/2019 | 11/7/2019 9:27:09 AM | A | PASS |
|
|
Final fire sprinkler inspection for scope of work complete.
Contact: Steven Vaughn Phone #: ###-#### Inspection requested via web by Hunter Fillmore
|
BLD19-03396
| FIRE-Final Inspection | 11/6/2019 | 11/7/2019 | 11/7/2019 9:08:18 AM | A | PASS |
|
|
Previously noted items have been corrected, no fire sprinkler modifications, fire alarm inspection is complete, fire extinguishers are placed with current inspection tags. Final life fire safety inspection for area of work complkete.
Jennifer Phone #: ###-####
|
BLD19-02279
| FIRE-Final Inspection | 11/7/2019 | 11/7/2019 | 11/7/2019 8:51:57 AM | P | PASS |
|
|
Fire sprinkler inspection is complete, fire alarm inspection is complete, fire extinguishers are placed with current inspection tags. Final life fire safety inspection for area of work complete.
Phone #: ###-#### Inspection requested via web by Korey Hall
|
FIR19-00680
| INSP-Final Inspection | 11/6/2019 | 11/7/2019 | 11/7/2019 8:50:56 AM | A | PASS |
|
|
Final fire alarm inspection for area of work is complete.
As early as possible Phone #: 2088301311 >> Inspection requested via mobile web by Nathan Price
|
FIR19-00634
| INSP-Final Inspection | 11/5/2019 | 11/7/2019 | 11/7/2019 8:04:05 AM | A | CANC |
|
|
We would like the inspection to be performed at 7:00 am per the request of the occupants. Please call Nate at ###-#### with inspection time. Phone #: ###-#### >> Inspection requested via web by Lori Brungardt Inspection cancelled from web by: Lori Brungardt
|