Inspections for the day of: Monday, November 8, 1999.
Number of inspections: 13
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJack Frank
TitleELE-INSPECTOR
Phone #794-1930
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE99-04000 Temporary Service11/4/199911/8/199911/8/1999 12:00:00 AMAPASS
BECKMAN ELEC ###-#### TEMP POLE T/S U/G new ok.
ELE99-03302 Electrical Rough-In11/5/199911/8/199911/8/1999 12:00:00 AMAPART
butch--- ###-#### ceiling insp R/I ceiling ok.
ELE99-03528 Final11/5/199911/8/199911/8/1999 12:00:00 AMPPASS
JOHN ###-#### FN INSP Final ok.
ELE99-04017 Electrical Rough-In11/5/199911/8/199911/8/1999 12:00:00 AMPFAIL
BRAD-- ###-#### R/I (JMS) Cor. Posted & called 334 radius of bend in MC cable.
ELE99-03980 Electrical Rough-In11/8/199911/8/199911/8/1999 12:00:00 AMPPASS
###-####-- vern Res. Rem. 1 rm ok
ELE99-02914 Final11/8/199911/8/199911/8/1999 12:00:00 AMPPASS
DAN--- ###-#### FN INSP Final ok.
ELE99-04025 Rough-In Permanent Service11/8/199911/8/199911/8/1999 12:00:00 AMPPASS
rick ###-#### 10 rooms a/c 100 amps (JMS) R/I & P/S ok
ELE99-04028 Rough-In Permanent Service11/8/199911/8/199911/8/1999 12:00:00 AMPPASS
BILL ###-#### R/I & SER (JMS) R/I & P/S ok
ELE99-03528 Final11/8/199911/8/199911/8/1999 12:00:00 AMPPASS
Final ok
ELE99-02914 Final11/8/199911/8/199911/8/1999 12:00:00 AMPPASS
Final ok
ELE99-04018 Permanent Service11/8/199911/8/199911/8/1999 12:00:00 AMPFAIL
Called cor. posted 250-66 shall provide 1/O copper GEC.
ELE99-04008 Electrical Rough-In11/5/199911/8/199911/5/1999 12:00:00 AMAPASS
MIKE--- ###-#### R/I R/I ok res. rem.
ELE99-03955 Electrical Rough-In11/5/199911/8/199911/5/1999 12:00:00 AMAPART
RANDY ###-#### R/I R/I of concrete encased electrode ok.