ELE05-04039
| Permanent Service | 11/8/2005 | 11/8/2005 | 11/8/2005 4:00:14 PM | P | PASS |
|
|
p/s o/h rec. ok
|
ELE05-04039
| Final | 11/8/2005 | 11/8/2005 | 11/8/2005 3:49:51 PM | P | CANC |
|
|
see added p/s
|
ELE05-03947
| Electrical Rough-In | 11/8/2005 | 11/8/2005 | 11/8/2005 3:00:18 PM | P | PASS |
|
|
I must of just missed you. I arrived at 8:45 am and noticed you had already been there. All issues should be taken care of. Thanks Tim; Phone #: ###-#### Internet Inspection Request from: Tim Lawrence ok cor. made
|
ELE05-01848
| Rough-In Permanent Service | 11/7/2005 | 11/8/2005 | 11/8/2005 2:14:32 PM | A | FAIL |
|
|
Contact Harvey Reyna; Phone #: ###-#### Internet Inspection Request from: HARVEY REYNA cor. called reinspection fee 210.52(A) outlet spacing, 312.5 needs conn. in garage for cable, 250.24&32 terminate GEC to neutral bus and install bond screw
|
ELE05-02596
| Final | 11/8/2005 | 11/8/2005 | 11/8/2005 1:32:35 PM | P | NH |
|
|
juan; Phone #: ###-#### Internet Inspection Request from: Letitia Mesa called left message no response talled shop they will reschedule
|
ELE05-03208
| Final | 11/8/2005 | 11/8/2005 | 11/8/2005 1:27:30 PM | P | NH |
|
|
L & K electric; Phone #: ###-#### Internet Inspection Request from: Letitia Mesa called also all violations not corrected
|
ELE05-04051
| Temporary Service | 11/7/2005 | 11/8/2005 | 11/8/2005 11:09:27 AM | A | FAIL |
|
|
###-#### H.Z. no address or ID sticker called
|
ELE05-03978
| Temporary Service | 11/7/2005 | 11/8/2005 | 11/8/2005 10:18:09 AM | A | PASS |
|
|
RON; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles ok
|
ELE05-04049
| Temporary Service | 11/7/2005 | 11/8/2005 | 11/8/2005 10:01:22 AM | A | FAIL |
|
|
please call shawn ###-#### when done inspection// cor. 250.24 connect GEC to neutral, 250.53(G) drive grd rod flush, 312,5 conn. for GEC called
|
ELE05-04040
| Final | 11/7/2005 | 11/8/2005 | 11/8/2005 9:40:40 AM | A | PASS |
|
|
###-#### - mitch Note: Hot tub ok
|
ELE05-03297
| Electrical Rough-In | 11/7/2005 | 11/8/2005 | 11/8/2005 9:11:42 AM | A | PASS |
|
|
Ceiling Re-inspection. ; Phone #: ###-#### Internet Inspection Request from: Steve Syltie both ceilings ok
|
ELE05-03947
| Electrical Rough-In | 11/7/2005 | 11/8/2005 | 11/8/2005 8:12:51 AM | A | FAIL |
|
|
Phone #: ###-#### Internet Inspection Request from: Tim Lawrence correction not made 300.4 nail plates and 11/4" reinspection fee due called
|