Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD05-02968 FIRE-Final Inspection11/8/200511/8/200511/8/2005 4:19:07 PMPFAIL
Fire dept access notes need to be addressed
FIR05-00210 INSP-Alarm Testing11/8/200511/8/200511/8/2005 4:18:31 PMPFAIL
a/v's need to have heights and cd ratings checked on all devices and then tested. Need to test all duct smoke detectors. Need to test fire sprinkler devices. The rolldown doors have been removed from the fire alarm system.
BLD05-02380 FIRE-Final Inspection11/7/200511/8/200511/8/2005 12:51:24 PMAFAIL
Replace the missing canopies on the sprinkler pendants and provide one fire extinguisher, tagged and mounted no higher than 48"
BLD05-01401 FIRE-Final Inspection11/7/200511/8/200511/8/2005 11:16:56 AMAPASS
Life safety finaled
BLD04-02934 FIRE-Final Inspection11/3/200511/8/200511/8/2005 10:16:18 AMAFAIL
Need fire alarm and fire sprinkler finaled. No items looked except the roll down doors which operated correctly.
FIR05-00727 INSP-Final Inspection10/26/200511/8/200511/8/2005 8:39:40 AMAFAIL
No test was performed due to lights not turning off under the hood and the suppression system not being connected to the fire alarm system.
FIR05-00598 INSP-Final Inspection11/4/200511/8/200511/8/2005 8:34:22 AMAFAIL
No access to the facp to shut down power to the duct smoke detector. No test performed.
FIR04-00004 INSP-Final Inspection11/3/200511/8/200511/8/2005 12:00:00 AMACANC