Inspections for the day of: Wednesday, November 8, 2006.
Number of inspections: 21
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR06-00645 INSP-Alarm Testing11/7/200611/8/200611/8/2006 4:08:23 PMAPART
Fire alarm at the waiting area only per field inspection by M.Timmerman is acceptable, noted four damper locations with no access provided to visually confirm closure of the vanes.
FIR05-00536 INSP-Sprinkler Rough-in/Hydro11/8/200611/8/200611/8/2006 4:05:22 PMPDONE
Duplicate inspection request for an AG hydrostatic test of the 1st floor east wing which passed.
FIR06-00628 INSP-Sprinkler Rough-in/Hydro11/7/200611/8/200611/8/2006 4:03:43 PMPPART
AG hydrostatic test of the wet and antifreeze systems are acceptable.
MIS06-00287 FIR-Final11/7/200611/8/200611/8/2006 4:02:42 PMAFAIL
Not all emergency lighting has been repaired for functionality as required.
FIR06-00558 INSP-Final Inspection11/7/200611/8/200611/8/2006 3:08:19 PMAPART
Fire sprinkler at the waiting area only as previously inspected is acceptable.
FIR05-00582 INSP-Sprinkler Rough-in/Hydro11/8/200611/8/200611/8/2006 2:48:09 PMPPART
AG hydrostatic test of the 1st floor east wing system is satisfactory.
FIR06-00726 INSP-Sprinkler Rough-in/Hydro11/7/200611/8/200611/8/2006 2:17:51 PMPPART
OH rough-in is acceptable, final pending system tie in, antifreeze fill, valve supervision and signage.
BLD06-02225 FIRE-Conference11/8/200611/8/200611/8/2006 12:48:03 PMPDONE
On site confrence to discuss areas lacking adequate fire sprinkler coverage.
FIR05-00425 INSP-Sprinkler Rough-in/Hydro11/7/200611/8/200611/8/2006 12:33:49 PMAPART
OH hydrostatic test of the 11th floor is acceptable.
FIR06-00808 INSP-Final Inspection11/7/200611/8/200611/8/2006 12:05:49 PMACANC
No time to complete inspection today.
FIR06-00820 INSP-Final Inspection11/1/200611/8/200611/8/2006 12:02:21 PMAPASS
c/n items have been completed, permit finaled.
BLD06-03001 FIRE-Final Inspection11/7/200611/8/200611/8/2006 11:41:42 AMAPASS
Fire life safety inspection passed.
BLD06-01480 FIRE-Final Inspection11/7/200611/8/200611/8/2006 11:12:22 AMAPASS
Inspection passed, tenant to mount the provided fire extinguisher on the wall as discussed for compliance prior to structural final.
FIR06-00605 INSP-Final Inspection11/8/200611/8/200611/8/2006 10:45:08 AMPFAIL
Need to provide method for locking or sealing the control valves at the backflow in the open position, also need to provide signage at the control valves indicating thier function, see fire code review notes for requirements.
BLD05-03335 FIRE-Final Inspection11/7/200611/8/200611/8/2006 10:39:57 AMAFAIL
Project related fire sprinkler permit failed final inspection.
FIR06-00795 INSP-Final Inspection11/7/200611/8/200611/8/2006 10:37:07 AMAPASS
Fire alarm work is acceptable, permit finaled.
FIR06-00794 INSP-Final Inspection11/7/200611/8/200611/8/2006 10:36:31 AMAPASS
Fire alarm work passed final inspection.
FIR06-00793 INSP-Final Inspection11/7/200611/8/200611/8/2006 10:35:59 AMAPASS
Fire alarm work passed final inspection.
BLD05-03105 FIRE-Final Inspection11/7/200611/8/200611/8/2006 10:35:29 AMAPASS
Shell fire life safety inspection is acceptable pending the installation of a visual indicator at the main entry/exit door at the 1st floor lobby south.
FIR06-00168 INSP-Final Inspection11/8/200611/8/200611/8/2006 10:33:21 AMPPASS
UG fire supply line permit finaled.
FIR06-00087 FIR-Aging Inspection11/8/200611/8/200611/8/2006 8:24:32 AM DEFR