ELE07-03679
| Electrical Rough-In | 11/8/2007 | 11/8/2007 | 11/8/2007 4:16:05 PM | P | PART |
|
|
ceiling cover, contact is Dan Ward ###-#### Phone #: ###-#### Internet Inspection Request from: Debby Ellis ok
|
ELE07-02309
| Electrical Rough-In | 11/8/2007 | 11/8/2007 | 11/8/2007 3:53:36 PM | P | PART |
|
|
contact Roger Reynolds Phone #: ###-#### Internet Inspection Request from: Debby Ellis ceilings ok
|
ELE07-03760
| Rough-In Permanent Service | 11/8/2007 | 11/8/2007 | 11/8/2007 3:16:21 PM | P | PASS |
|
|
gene; Phone #: ###-#### Internet Inspection Request from: Barbara Stitt r/i p/s u/g new ok
|
ELE07-03705
| Permanent Service | 11/8/2007 | 11/8/2007 | 11/8/2007 2:32:19 PM | P | PASS |
|
|
andy Phone #: ###-#### p/s o/h rec. ok
|
ELE07-01089
| Final | 11/8/2007 | 11/8/2007 | 11/8/2007 12:39:46 PM | P | PASS |
|
|
final on kitchen, any question call Tate @ ###-#### Phone #: ###-#### Internet Inspection Request from: Andy Rose ok
|
ELE07-02774
| Final | 11/8/2007 | 11/8/2007 | 11/8/2007 12:39:26 PM | P | PASS |
|
|
final on new addition, any questions call Tate @ ###-#### Phone #: ###-#### Internet Inspection Request from: Andy Rose ok called survey posted needs totally enclosed fixture upstairs closet
|
ELE07-03455
| Final | 11/7/2007 | 11/8/2007 | 11/8/2007 10:41:47 AM | A | PASS |
|
|
Scheduled by a contractor via Hello! on 11/7/2007 at 12:07:31 PM. Contact: ###-####. ok card signed
|
ELE07-03589
| Final | 11/8/2007 | 11/8/2007 | 11/8/2007 9:55:59 AM | A | PASS |
|
|
Scheduled by a contractor via Hello! on 11/8/2007 at 5:43:59 AM. Contact: ###-####. ok
|
ELE07-03736
| Electrical Rough-In | 11/7/2007 | 11/8/2007 | 11/8/2007 9:16:19 AM | A | PASS |
|
|
clyde Phone #: ###-#### ok
|
ELE07-03734
| Electrical Rough-In | 11/6/2007 | 11/8/2007 | 11/8/2007 8:54:36 AM | A | FAIL |
|
|
Mike McCarrel Electrician Homeowner Ann McCuistion ###-#### Phone #: ###-#### Internet Inspection Request from: Jim Burnette corr. called 314.3 metallic raceway allowed in plastic box, 300.4 nail plates garage, 408.4 panel schedule bo specific, 408.7 seal breaker KO, 225.31&36 exception shed needs disconnect
|
ELE06-03975
| Final | 11/8/2007 | 11/8/2007 | 11/8/2007 8:06:23 AM | A | PASS |
|
|
ok corrections made
|