Inspections for the day of: Thursday, November 8, 2007.
Number of inspections: 12
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorBob Reichert
TitleELE-INSPECTOR
Phone #794-1923
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE07-02792 ELE-Aging Inspection11/8/200711/8/200711/16/2007 10:36:40 AM DONE
called contractor to call for inspection
ELE07-03618 Final11/7/200711/8/200711/9/2007 8:32:23 AMAPASS
Phone #: ###-#### Internet Inspection Request from: joe wheeler ok to final, signed occ card
ELE07-02928 Final11/7/200711/8/200711/8/2007 3:38:21 PMPCANC
neal Phone #: ###-#### called contractor and told that ele and bld permit addresses must match and also posted house address
ELE07-02927 Final11/7/200711/8/200711/8/2007 3:37:06 PMPCANC
neal Phone #: ###-#### called contractor, explained that addresses must match bld, ele permits and actual house as posted
ELE07-03759 Rough-In Permanent Service11/8/200711/8/200711/8/2007 2:56:22 PMPFAIL
Phone #: ###-#### Internet Inspection Request from: Ryan Christensen caleed, left correction notice, nec 330.30(B) mc cable shall be strapped within 12' of box, 258.30(A) emt shall be supported within 3' of box, 300.4(A)&(D) edge of bored holes and raceways shall be 1 1/4" from edge of framing members
ELE07-01506 Final11/8/200711/8/200711/8/2007 12:45:18 PMPPASS
Scheduled by a contractor via Hello! on 11/8/2007 at 9:04:31 AM. Contact: ###-####. corrections made, ok to final
ELE07-03747 Final11/8/200711/8/200711/8/2007 12:16:45 PMPCANC
Mike; Phone #: ###-#### Internet Inspection Request from: Cathy Weisshaupt see t/s
ELE07-03747 Temporary Service11/8/200711/8/200711/8/2007 12:07:33 PMPPASS
Mike; Phone #: ###-#### Internet Inspection Request from: Cathy Weisshaupt corrections made, t/s o/h n ok
ELE07-03214 Electrical Rough-In11/7/200711/8/200711/8/2007 11:59:41 AMPPASS
reception desk Phone #: ###-#### Internet Inspection Request from: Kerri Hamilton ok to cover reception desk only
ELE07-03747 Temporary Service11/7/200711/8/200711/8/2007 9:54:58 AMAFAIL
mike Phone #: ###-#### called, left correction notice, nec 250.24(A) gec shall connect to grounded service conductor, 250.53(G) upper end of electrode shall be flush with or below ground level, 250.24(B) shall instasll main bonding jumper
ELE06-04373 Final11/7/200711/8/200711/8/2007 9:09:24 AMAFAIL
Please call for access information--shane; Phone #: ###-#### Internet Inspection Request from: Barbara Stitt called contractor, left correction notice, nec 210.70(A)(3) shall provide lighting outlet in basement room with equipment requiring servicing, 210.52(B)(2) shall not have outside rear receptacle on small appliance branch circuit, 110.12(A) shall close unused opening in a/c disconnect, 406.4 kitchen recpt shall be securely mounted, 422.31(B) shall provide disconnect with lockout for water heater
ELE07-02095 Final11/7/200711/8/200711/8/2007 8:24:18 AMAFAIL
skip Phone #: ###-#### met contractor, left correction notice, nec 300.11(B) shall not suport low voltage wiring from raceways,314.25 in completed installations, boxes shall have covers installed, 400.8 shall not use cord above dropped ceiling