ELE07-02792
| ELE-Aging Inspection | 11/8/2007 | 11/8/2007 | 11/16/2007 10:36:40 AM | | DONE |
|
|
called contractor to call for inspection
|
ELE07-03618
| Final | 11/7/2007 | 11/8/2007 | 11/9/2007 8:32:23 AM | A | PASS |
|
|
Phone #: ###-#### Internet Inspection Request from: joe wheeler ok to final, signed occ card
|
ELE07-02928
| Final | 11/7/2007 | 11/8/2007 | 11/8/2007 3:38:21 PM | P | CANC |
|
|
neal Phone #: ###-#### called contractor and told that ele and bld permit addresses must match and also posted house address
|
ELE07-02927
| Final | 11/7/2007 | 11/8/2007 | 11/8/2007 3:37:06 PM | P | CANC |
|
|
neal Phone #: ###-#### called contractor, explained that addresses must match bld, ele permits and actual house as posted
|
ELE07-03759
| Rough-In Permanent Service | 11/8/2007 | 11/8/2007 | 11/8/2007 2:56:22 PM | P | FAIL |
|
|
Phone #: ###-#### Internet Inspection Request from: Ryan Christensen caleed, left correction notice, nec 330.30(B) mc cable shall be strapped within 12' of box, 258.30(A) emt shall be supported within 3' of box, 300.4(A)&(D) edge of bored holes and raceways shall be 1 1/4" from edge of framing members
|
ELE07-01506
| Final | 11/8/2007 | 11/8/2007 | 11/8/2007 12:45:18 PM | P | PASS |
|
|
Scheduled by a contractor via Hello! on 11/8/2007 at 9:04:31 AM. Contact: ###-####. corrections made, ok to final
|
ELE07-03747
| Final | 11/8/2007 | 11/8/2007 | 11/8/2007 12:16:45 PM | P | CANC |
|
|
Mike; Phone #: ###-#### Internet Inspection Request from: Cathy Weisshaupt see t/s
|
ELE07-03747
| Temporary Service | 11/8/2007 | 11/8/2007 | 11/8/2007 12:07:33 PM | P | PASS |
|
|
Mike; Phone #: ###-#### Internet Inspection Request from: Cathy Weisshaupt corrections made, t/s o/h n ok
|
ELE07-03214
| Electrical Rough-In | 11/7/2007 | 11/8/2007 | 11/8/2007 11:59:41 AM | P | PASS |
|
|
reception desk Phone #: ###-#### Internet Inspection Request from: Kerri Hamilton ok to cover reception desk only
|
ELE07-03747
| Temporary Service | 11/7/2007 | 11/8/2007 | 11/8/2007 9:54:58 AM | A | FAIL |
|
|
mike Phone #: ###-#### called, left correction notice, nec 250.24(A) gec shall connect to grounded service conductor, 250.53(G) upper end of electrode shall be flush with or below ground level, 250.24(B) shall instasll main bonding jumper
|
ELE06-04373
| Final | 11/7/2007 | 11/8/2007 | 11/8/2007 9:09:24 AM | A | FAIL |
|
|
Please call for access information--shane; Phone #: ###-#### Internet Inspection Request from: Barbara Stitt called contractor, left correction notice, nec 210.70(A)(3) shall provide lighting outlet in basement room with equipment requiring servicing, 210.52(B)(2) shall not have outside rear receptacle on small appliance branch circuit, 110.12(A) shall close unused opening in a/c disconnect, 406.4 kitchen recpt shall be securely mounted, 422.31(B) shall provide disconnect with lockout for water heater
|
ELE07-02095
| Final | 11/7/2007 | 11/8/2007 | 11/8/2007 8:24:18 AM | A | FAIL |
|
|
skip Phone #: ###-#### met contractor, left correction notice, nec 300.11(B) shall not suport low voltage wiring from raceways,314.25 in completed installations, boxes shall have covers installed, 400.8 shall not use cord above dropped ceiling
|