FIR07-00796
| INSP-Final Inspection | 11/8/2007 | 11/8/2007 | 11/9/2007 9:33:46 AM | P | PART |
|
|
Ok to cover over head In kitchen area due to the change in design in sprinkler system, changes were made to the revised set of approved plans.KR
|
FIR07-00723
| INSP-Final Inspection | 11/8/2007 | 11/8/2007 | 11/8/2007 7:44:12 PM | P | PASS |
|
|
|
FIR07-00723
| INSP-Final Inspection | 11/7/2007 | 11/8/2007 | 11/8/2007 7:33:26 PM | P | PASS |
|
|
Test clean agent panel for monitoring of preaction system and interconnection to main fire alarm panel.KR
|
FIR07-00706
| INSP-Final Inspection | 11/6/2007 | 11/8/2007 | 11/8/2007 7:26:22 PM | P | CANC |
|
|
complete test of fire alarm panel duct smokes,flow and tamper switches and interconnnetion to clean agent fike panel.KR
|
FIR07-00755
| INSP-Final Inspection | 11/7/2007 | 11/8/2007 | 11/8/2007 7:18:05 PM | P | PASS |
|
|
Do a full function test on preaction system.Verifie flow, tamper and alarm to main panel and clean agent fike panel.
|
BLD07-00429
| FIRE-Final Inspection | 11/8/2007 | 11/8/2007 | 11/8/2007 6:07:52 PM | P | PASS |
|
|
Fire life safety passed per K. Roule.
|
FIR07-00661
| INSP-Sprinkler Rough-in/Hydro | 11/8/2007 | 11/8/2007 | 11/8/2007 6:05:59 PM | P | PART |
|
|
Work completed is outside this permit scope, notified contractor to obtain a quick permit for the six relcoated heads at the first floor hallway.
|
FIR07-00905
| INSP-Sprinkler Rough-in | 11/8/2007 | 11/8/2007 | 11/8/2007 6:03:43 PM | P | FAIL |
|
|
Plans and permit documents for the UG work could not be located on site at the time of inspection, also noted depth of bury at some locations does not meet min. 4'6" (2"-6" shallow).
|
FIR07-00700
| INSP-Final Inspection | 11/8/2007 | 11/8/2007 | 11/8/2007 5:58:53 PM | P | PART |
|
|
OH rough-in inspection passed, noted overhead door is located opposite from what is indicated on approved plan set.
|
BLD07-02244
| FIRE-Final Inspection | 11/7/2007 | 11/8/2007 | 11/8/2007 5:56:34 PM | A | PART |
|
|
Fire life safety is acceptable for the 3rd floor NE quad per site inspection completed by K. Roule.
|
FIR06-00595
| INSP-Alarm Testing | 11/7/2007 | 11/8/2007 | 11/8/2007 3:34:41 PM | A | PART |
|
|
FA testing for the 3rd floor NE quad passed per K. Roule.
|
FIR07-00826
| INSP-Final Inspection | 11/8/2007 | 11/8/2007 | 11/8/2007 3:32:11 PM | P | PASS |
|
|
Fire sprinkler permit finaled.
|
FIR07-00134
| INSP-Final Inspection | 11/7/2007 | 11/8/2007 | 11/8/2007 3:31:38 PM | A | PASS |
|
|
Corrections are complete, fire sprinkler permit finaled.
|
FIR07-00106
| INSP-Final Inspection | 11/7/2007 | 11/8/2007 | 11/8/2007 3:31:02 PM | A | PASS |
|
|
Corrections are complete, fire sprinkler permit finaled.
|
FIR07-00826
| INSP-Sprinkler Rough-in | 11/7/2007 | 11/8/2007 | 11/8/2007 2:40:09 PM | A | PASS |
|
|
Fire sprinkler work is satisfactory per inspection completed by K. Roule.
|
BLD07-02345
| FIRE-Final Inspection | 11/5/2007 | 11/8/2007 | 11/8/2007 2:32:48 PM | P | PART |
|
|
Fire life safety final pending project related fire alarm permit final, remaining scope of work is acceptable.
|
BLD07-02475
| FIRE-Final Inspection | 11/7/2007 | 11/8/2007 | 11/8/2007 2:29:22 PM | A | FAIL |
|
|
Need to add exit signs at locations as discussed, EM lighting at two locations is not functional, PFE's are okay, will test remaider of EM lighting at next inspection.
|
FIR07-00590
| INSP-Sprinkler Rough-in | 11/7/2007 | 11/8/2007 | 11/8/2007 2:27:17 PM | A | PART |
|
|
OH rough-in is acceptable for cover per the scope of permit work.
|
FIR07-00414
| FIR-Aging Inspection | 11/8/2007 | 11/8/2007 | 11/8/2007 7:49:09 AM | | DEFR |
|
|
Under construction.
|
FIR07-00531
| INSP-Sprinkler Rough-in | 11/2/2007 | 11/8/2007 | 11/5/2007 1:08:34 PM | P | CANC |
|
|
mikw Phone #: ###-#### Inspection cancelled from web by: Patricia Smith
|