Inspections for the day of: Thursday, November 8, 2007.
Number of inspections: 10
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR07-00380 INSP-Final Inspection11/7/200711/8/200711/9/2007 3:52:45 PMAPASS
Permit is ok to final per Mike Timmerman.
FIR06-00011 INSP-Alarm Testing11/7/200711/8/200711/8/2007 2:32:25 PMPCANC
Overbooked. I notified brian that this would need to be rescheduled.
BLD07-01225 FIRE-Final Inspection11/7/200711/8/200711/8/2007 2:30:45 PMAFAIL
Provide address on building where is can be viewable as discussed, provide power so the exit sign and emergency lighting can be tested, provide remote annunciators and manometer tests for the duct smoke detectors and repair the curb painting as discussed.
BLD07-01226 FIRE-Final Inspection11/7/200711/8/200711/8/2007 12:34:35 PMAFAIL
Provide address on both sides of building where is can be viewable as discussed, provide power so the exit sign and emergency lighting can be tested.
BLD07-01485 FIRE-Final Inspection11/8/200711/8/200711/8/2007 12:24:10 PMPPASS
Life safety passed.
FIR07-00578 INSP-Sprinkler Rough-in11/7/200711/8/200711/8/2007 10:38:25 AMAPASS
See the city approved plans for piping locations that are approved for cover. They will have todays date.
FIR07-00842 INSP-Final Inspection11/7/200711/8/200711/8/2007 10:14:15 AMAFAIL
Provide updated map for the facp and change the zone 5 to state duct detector not tamper
FIR07-00843 INSP-Final Inspection11/7/200711/8/200711/8/2007 10:11:12 AMAFAIL
Provide updated map for the facp and change the zone 5 to state duct detector not tamper
BLD07-02527 FIRE-Final Inspection11/8/200711/8/200711/8/2007 9:30:09 AMAPASS
life safety passed
FIR07-00852 INSP-Sprinkler Rough-in11/7/200711/8/200711/8/2007 8:36:19 AMAPASS
The air compressor test passed. The permit is ready to final again.