FIR12-00365
| INSP-Sprinkler Rough-in | 11/8/2012 | 11/8/2012 | 11/8/2012 3:44:54 PM | P | CANC |
|
|
Cancel per Perly Daniel
|
BLD12-02043
| FIRE-Final Inspection | 11/8/2012 | 11/8/2012 | 11/8/2012 3:30:14 PM | P | FAIL |
|
|
Life safety will be ok to sign off when the project related fire alarm permit is finaled. I noted that the keyed lock at the new double doors will need an indicator installed prior to the building inspector sign off.
|
FIR12-00611
| INSP-Final Inspection | 11/8/2012 | 11/8/2012 | 11/8/2012 3:27:38 PM | P | PASS |
|
|
Permit finaled
|
FIR12-00477
| INSP-Final Inspection | 11/7/2012 | 11/8/2012 | 11/8/2012 2:53:50 PM | P | PASS |
|
|
Permit finaled
|
FIR12-00547
| INSP-Final Inspection | 11/8/2012 | 11/8/2012 | 11/8/2012 2:52:16 PM | P | FAIL |
|
|
The new duct smoke detectors are powered from the fire alarm control panel which is not noted on the plans. Per the plan reviewer revised calculations are required showing the addtional power loss prior to a final sign off. HVAC units were tested for shutdown which passed.
|
BLD12-01461
| FIRE-Conference | 11/7/2012 | 11/8/2012 | 11/8/2012 11:43:25 AM | A | DONE |
|
|
Dave and I went over the life safety notes and specifically the placement of the fire extinguishers.
|
FIR12-00582
| INSP-Sprinkler Rough-in | 11/7/2012 | 11/8/2012 | 11/8/2012 11:12:12 AM | A | PASS |
|
|
Three of the five underground supplies are ok for cover. See the city approved plans for locations.
|
FIR12-00288
| INSP-Final Inspection | 11/8/2012 | 11/8/2012 | 11/8/2012 10:26:35 AM | P | PART |
|
|
A temporary occupancy was given until the fire sprinkler corrections have been addressed.
|
FIR12-00174
| INSP-Final Inspection | 11/8/2012 | 11/8/2012 | 11/8/2012 10:26:13 AM | P | PART |
|
|
A temporary occupancy was given until the fire sprinkler corrections have been addressed.
|
FIR12-00431
| INSP-Alarm Testing | 11/7/2012 | 11/8/2012 | 11/8/2012 10:25:20 AM | A | PART |
|
|
A temporary occupancy was given until the fire alarm permit/correction issues have been addressed.
|
BLD11-03012
| FIRE-Final Inspection | 11/7/2012 | 11/8/2012 | 11/8/2012 9:13:32 AM | A | PART |
|
|
Temporary occupancy is approved with Scott Arellano's permission until the fire alarm and fire sprinkler permits have been addressed.
|