3rd floor Hall,Storage , comm rm and Units 301 , 302 , 303 , 304 , 305 , 306 , 307 , 308 , 309 , 310 , 311 , 312 , 313 , 314 , 315 , 316 , 317 , 318 , 319 Call Craig Phone #: ###-#### Inspection requested via web by Tom Betty 301- 250.52- walls 24" and wider shall have a receptacle outlet installed in bedroom. 309- 210.52(A)- Receptacles required by this article shall be energized continuously. Permitted switched receptacles shall only switch 1/2 of receptacle. Corridor comm room- 408.4- Circuit directory shall be complete for panel in this room. 302, 303, 304, 305, 306, 307, 308, 310, 311, 312, 313, 314, 315, 316, 317, 317, 318, 319, corridor and storage rooms TCO ok
|