MEC18-05264
| Rough-in | 11/8/2018 | 11/8/2018 | 11/8/2018 3:39:29 PM | P | FAIL |
|
|
Mechanical ; Gas Log Phone #: ###-#### Inspection requested via web by Jon VanderStelt - fresh air cant be tied in at return can. move to return duct at furnace- need to see line set R/I at house
|
MEC18-05264
| Pressure Test | 11/8/2018 | 11/8/2018 | 11/8/2018 3:37:14 PM | P | PASS |
|
|
Mechanical ; Gas Log Phone #: ###-#### Inspection requested via web by Jon VanderStelt - 5lb flue pressure test ok- 20lb gas pressure test ok
|
MEC18-05387
| Pressure Test | 11/8/2018 | 11/8/2018 | 11/8/2018 3:14:58 PM | P | PART |
|
|
Phone #: ###-#### Inspection requested via web by Oleg Chervak - 5lb flue pressure test fail need to retest- 20lb gas pressure test ok
|
MEC18-05387
| Rough-in | 11/8/2018 | 11/8/2018 | 11/8/2018 3:14:17 PM | P | PART |
|
|
mec and firepl Phone #: ###-#### Inspection requested via web by Oleg Chervak - R/I ok- need to retest 5lb flue test- and fix rip in insulation above garage
|
MEC18-05326
| Final | 11/7/2018 | 11/8/2018 | 11/8/2018 2:31:57 PM | P | PASS |
|
|
Later PM if possible. Chuck ###-#### Phone #: ###-#### Inspection requested via web by Arielle Hendricks- RTU's final ok
|
MEC18-05326
| Pressure Test | 11/7/2018 | 11/8/2018 | 11/8/2018 2:31:33 PM | P | CANC |
|
|
Later PM if possible. Chuck ###-#### Phone #: ###-#### Inspection requested via web by Arielle Hendricks- no pressure test needed
|
MEC18-05320
| Final | 11/6/2018 | 11/8/2018 | 11/8/2018 2:01:21 PM | P | PASS |
|
|
installer Jarod ###-#### Phone #: ###-#### Inspection requested via web by Aaron Alandt -furnace ac coil co ok
|
MEC18-05320
| Pressure Test | 11/6/2018 | 11/8/2018 | 11/8/2018 2:01:00 PM | P | PASS |
|
|
installer Jarod ###-#### Phone #: ###-#### Inspection requested via web by Aaron Alandt 5lb flue pressure test ok- 20 lb gas pressure test ok for range
|
MEC18-05327
| Final | 11/7/2018 | 11/8/2018 | 11/8/2018 1:48:09 PM | P | PASS |
|
|
Please call Craig prior to arrival ###-#### Phone #: ###-#### Inspection requested via web by Arielle Hendricks-furnace only co ok- duct work ok
|
MEC18-05389
| Pressure Test | 11/8/2018 | 11/8/2018 | 11/8/2018 1:20:16 PM | P | PASS |
|
|
Adam: ###-#### Phone #: ###-#### Inspection requested via web by Frank Marturello - 5lb and 20lb ok
|
MEC18-05389
| Rough-in | 11/8/2018 | 11/8/2018 | 11/8/2018 1:19:21 PM | P | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Frank Marturello- R/I ok
|
MEC18-04670
| Final | 11/7/2018 | 11/8/2018 | 11/8/2018 1:18:38 PM | P | PASS |
|
|
This is a Flue Pressure and Final Inspect. Please meet our installer at home at 1:30 PM. Contact for Right Now is Mary ###-#### Phone #: ###-#### Inspection requested via web by Mary LaFayette - 5lb flue ok- furnace ac coil co ok
|
MEC18-05352
| Final | 11/7/2018 | 11/8/2018 | 11/8/2018 11:39:41 AM | A | PASS |
|
|
I will be there to meet you... Inspection requested via web by jeff jedlick- furnace ac coil co ok
|
MEC18-05010
| Rough-in | 11/7/2018 | 11/8/2018 | 11/8/2018 10:57:47 AM | A | PASS |
|
|
ROSE ###-#### Phone #: ###-#### Inspection requested via web by Mike Almanza- R/I ok
|
MEC18-05358
| Final | 11/7/2018 | 11/8/2018 | 11/8/2018 10:43:10 AM | A | FAIL |
|
|
Phone #: ###-#### Inspection requested via web by Kim Lithander- need to pulled plumbing permit for water softener- furnace only co ok- when plumbing permit gets pulled re schedule mec permit for final
|
MEC18-04705
| Rough-in | 11/7/2018 | 11/8/2018 | 11/8/2018 10:24:44 AM | A | PASS |
|
|
kitchen toekick is part of the fantech system for crawl // Terek Phone #: ###-####- R/I ok
|
MEC18-04705
| Pressure Test | 11/7/2018 | 11/8/2018 | 11/8/2018 10:24:25 AM | A | PASS |
|
|
Terek Phone #: ###-####- 5lb flue pressure test ok
|
MEC18-05323
| Final | 11/7/2018 | 11/8/2018 | 11/8/2018 10:12:00 AM | A | FAIL |
|
|
Phone #: ###-#### Inspection requested via web by Mary LaFayette- furnace needs a disconnect located within sight- everything else is ok
|
MEC18-05309
| Final | 11/7/2018 | 11/8/2018 | 11/8/2018 10:09:10 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Mary LaFayette- furnace only co ok
|
MEC18-05308
| Final | 11/5/2018 | 11/8/2018 | 11/8/2018 9:35:31 AM | A | PASS |
|
|
Please call Holly or Dan (###-####) 30 minutes prior to showing up, Thank you Phone #: ###-#### Inspection requested via web by Tyler Collado- furnace only ok
|
MEC18-01885
| Final | 11/7/2018 | 11/8/2018 | 11/8/2018 9:23:52 AM | A | FAIL |
|
|
Ken ###-#### Phone #: ###-#### Inspection requested via web by Arielle Hendricks- range vent cant be flex needs to be smooth walled pipe
|
MEC18-04929
| Pressure Test | 11/7/2018 | 11/8/2018 | 11/8/2018 9:11:41 AM | A | PASS |
|
|
late AM inspection if possible please. thank you! pressure test on flue Phone #: ###-#### Inspection requested via web by Aaron Alandt - 5lb flue pressure test ok
|
MEC18-03087
| Rough-in | 11/7/2018 | 11/8/2018 | 11/8/2018 8:55:45 AM | A | FAIL |
|
|
partial and questions - Thomas Phone #: ###-####- this was a 100lb hydronics pressure test- need proper size gauge and needs to be at least 100lb- talked with home owner about gas pipe sizing to boiler
|