Inspections for the day of: Thursday, November 8, 2018.
Number of inspections: 23
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJack Reynolds
TitleMEC INSPECTOR
Phone #208-803-2395
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
MEC18-05264 Rough-in11/8/201811/8/201811/8/2018 3:39:29 PMPFAIL
Mechanical ; Gas Log Phone #: ###-#### Inspection requested via web by Jon VanderStelt
- fresh air cant be tied in at return can. move to return duct at furnace- need to see line set R/I at house
MEC18-05264 Pressure Test11/8/201811/8/201811/8/2018 3:37:14 PMPPASS
Mechanical ; Gas Log Phone #: ###-#### Inspection requested via web by Jon VanderStelt
- 5lb flue pressure test ok- 20lb gas pressure test ok
MEC18-05387 Pressure Test11/8/201811/8/201811/8/2018 3:14:58 PMPPART
Phone #: ###-#### Inspection requested via web by Oleg Chervak
- 5lb flue pressure test fail need to retest- 20lb gas pressure test ok
MEC18-05387 Rough-in11/8/201811/8/201811/8/2018 3:14:17 PMPPART
mec and firepl Phone #: ###-#### Inspection requested via web by Oleg Chervak
- R/I ok- need to retest 5lb flue test- and fix rip in insulation above garage
MEC18-05326 Final11/7/201811/8/201811/8/2018 2:31:57 PMPPASS
Later PM if possible. Chuck ###-#### Phone #: ###-#### Inspection requested via web by Arielle Hendricks- RTU's final ok
MEC18-05326 Pressure Test11/7/201811/8/201811/8/2018 2:31:33 PMPCANC
Later PM if possible. Chuck ###-#### Phone #: ###-#### Inspection requested via web by Arielle Hendricks- no pressure test needed
MEC18-05320 Final11/6/201811/8/201811/8/2018 2:01:21 PMPPASS
installer Jarod ###-#### Phone #: ###-#### Inspection requested via web by Aaron Alandt
-furnace ac coil co ok
MEC18-05320 Pressure Test11/6/201811/8/201811/8/2018 2:01:00 PMPPASS
installer Jarod ###-#### Phone #: ###-#### Inspection requested via web by Aaron Alandt
5lb flue pressure test ok- 20 lb gas pressure test ok for range
MEC18-05327 Final11/7/201811/8/201811/8/2018 1:48:09 PMPPASS
Please call Craig prior to arrival ###-#### Phone #: ###-#### Inspection requested via web by Arielle Hendricks-furnace only co ok- duct work ok
MEC18-05389 Pressure Test11/8/201811/8/201811/8/2018 1:20:16 PMPPASS
Adam: ###-#### Phone #: ###-#### Inspection requested via web by Frank Marturello
- 5lb and 20lb ok
MEC18-05389 Rough-in11/8/201811/8/201811/8/2018 1:19:21 PMPPASS
Phone #: ###-#### Inspection requested via web by Frank Marturello- R/I ok
MEC18-04670 Final11/7/201811/8/201811/8/2018 1:18:38 PMPPASS
This is a Flue Pressure and Final Inspect. Please meet our installer
at home at 1:30 PM. Contact for Right Now is Mary ###-####
Phone #: ###-#### Inspection requested via web by Mary LaFayette
- 5lb flue ok- furnace ac coil co ok
MEC18-05352 Final11/7/201811/8/201811/8/2018 11:39:41 AMAPASS
I will be there to meet you... Inspection requested via web by jeff jedlick- furnace ac coil co ok
MEC18-05010 Rough-in11/7/201811/8/201811/8/2018 10:57:47 AMAPASS
ROSE ###-#### Phone #: ###-#### Inspection requested via web by Mike Almanza- R/I ok
MEC18-05358 Final11/7/201811/8/201811/8/2018 10:43:10 AMAFAIL
Phone #: ###-#### Inspection requested via web by Kim Lithander- need to pulled plumbing permit for water softener- furnace only co ok- when plumbing permit gets pulled re schedule mec permit for final
MEC18-04705 Rough-in11/7/201811/8/201811/8/2018 10:24:44 AMAPASS
kitchen toekick is part of the fantech system for crawl // Terek Phone #: ###-####- R/I ok
MEC18-04705 Pressure Test11/7/201811/8/201811/8/2018 10:24:25 AMAPASS
Terek Phone #: ###-####- 5lb flue pressure test ok
MEC18-05323 Final11/7/201811/8/201811/8/2018 10:12:00 AMAFAIL
Phone #: ###-#### Inspection requested via web by Mary LaFayette- furnace needs a disconnect located within sight- everything else is ok
MEC18-05309 Final11/7/201811/8/201811/8/2018 10:09:10 AMAPASS
Phone #: ###-#### Inspection requested via web by Mary LaFayette- furnace only co ok
MEC18-05308 Final11/5/201811/8/201811/8/2018 9:35:31 AMAPASS
Please call Holly or Dan (###-####) 30 minutes prior to showing up, Thank you Phone #: ###-#### Inspection requested via web by Tyler Collado- furnace only ok
MEC18-01885 Final11/7/201811/8/201811/8/2018 9:23:52 AMAFAIL
Ken ###-#### Phone #: ###-#### Inspection requested via web by Arielle Hendricks- range vent cant be flex needs to be smooth walled pipe
MEC18-04929 Pressure Test11/7/201811/8/201811/8/2018 9:11:41 AMAPASS
late AM inspection if possible please. thank you!
pressure test on flue Phone #: ###-#### Inspection requested via web by Aaron Alandt
- 5lb flue pressure test ok
MEC18-03087 Rough-in11/7/201811/8/201811/8/2018 8:55:45 AMAFAIL
partial and questions - Thomas Phone #: ###-####- this was a 100lb hydronics pressure test- need proper size gauge and needs to be at least 100lb- talked with home owner about gas pipe sizing to boiler