Inspections for the day of: Wednesday, November 9, 2005.
Number of inspections: 10
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJack Frank
TitleELE-INSPECTOR
Phone #794-1930
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE05-03208 Final11/9/200511/9/200511/9/2005 4:29:23 PMPFAIL
darla; Phone #: ###-####(Steve L&K ###-####) Internet Inspection Request from: Cathy Chiles cor. posted called, 250.52(A)(1) or104(A)(1) grd or bond water system at p/s, 240.24(A) p/s panel shall be set so no breaker when installed will be more than 6ft 7" to handle, posted 5 working days to start on violations or civil action may be taken
ELE05-03484 Final11/9/200511/9/200511/9/2005 2:16:58 PMPPART
gayle; Phone #: ###-#### Internet Inspection Request from: Letitia Mesa r/i ok corrections made, still needs to terminate GEC to equip grd bus 250.32(B)(1)
ELE05-04047 Rough-In Permanent Service11/7/200511/9/200511/9/2005 1:19:47 PMPFAIL
steve ###-#### cor. called left message 300.4 nail plates, 11/4" inside outside of framing members, 312.5 conn for grd wire at p/s, uncover u/g from house to garage install outside front recept box do not cover posted
ELE05-03906 Electrical Rough-In11/9/200511/9/200511/9/2005 12:41:56 PMPPASS
trench inspection///vivian; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie ok u/g house to garage
ELE05-03299 ELE-Aging Inspection11/9/200511/9/200511/9/2005 10:01:41 AM PART
called left message
ELE05-04048 Electrical Rough-In11/8/200511/9/200511/9/2005 9:37:11 AMAPART
bonding on new swimming pool and wiring for pool pump. Internet Inspection Request from: Andy Rose ok e grid ok also
ELE05-04051 Temporary Service11/8/200511/9/200511/9/2005 9:11:21 AMAFAIL
HZ; Phone #: ###-#### Internet Inspection Request from: Barbara Moore cor. called 250.24 shall make connection between grd and neutral
ELE05-02596 Final11/8/200511/9/200511/9/2005 8:41:52 AMAFAIL
warren; Phone #: ###-#### Internet Inspection Request from: Letitia Mesa
110.3 shall not use cable ties to secure flex, 300.10 & 314.3 shall install bonding means or use non metallic raceways where non metallic enclosures encountered met contractor at site
ELE05-04038 Rough-In Permanent Service11/7/200511/9/200511/8/2005 7:42:25 PMPCANC
Rough in for underground conduit only. ; Phone #: ###-#### Internet Inspection Request from: Randy Fletcher Inspection cancelled from web by: Randy Fletcher
ELE05-04057 Final11/8/200511/9/200511/8/2005 2:20:35 PMACANC
Phone #: ###-#### Internet Inspection Request from: Dana Moyer Inspection cancelled from web by: Dana Moyer