ELE05-03208
| Final | 11/9/2005 | 11/9/2005 | 11/9/2005 4:29:23 PM | P | FAIL |
|
|
darla; Phone #: ###-####(Steve L&K ###-####) Internet Inspection Request from: Cathy Chiles cor. posted called, 250.52(A)(1) or104(A)(1) grd or bond water system at p/s, 240.24(A) p/s panel shall be set so no breaker when installed will be more than 6ft 7" to handle, posted 5 working days to start on violations or civil action may be taken
|
ELE05-03484
| Final | 11/9/2005 | 11/9/2005 | 11/9/2005 2:16:58 PM | P | PART |
|
|
gayle; Phone #: ###-#### Internet Inspection Request from: Letitia Mesa r/i ok corrections made, still needs to terminate GEC to equip grd bus 250.32(B)(1)
|
ELE05-04047
| Rough-In Permanent Service | 11/7/2005 | 11/9/2005 | 11/9/2005 1:19:47 PM | P | FAIL |
|
|
steve ###-#### cor. called left message 300.4 nail plates, 11/4" inside outside of framing members, 312.5 conn for grd wire at p/s, uncover u/g from house to garage install outside front recept box do not cover posted
|
ELE05-03906
| Electrical Rough-In | 11/9/2005 | 11/9/2005 | 11/9/2005 12:41:56 PM | P | PASS |
|
|
trench inspection///vivian; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie ok u/g house to garage
|
ELE05-03299
| ELE-Aging Inspection | 11/9/2005 | 11/9/2005 | 11/9/2005 10:01:41 AM | | PART |
|
|
called left message
|
ELE05-04048
| Electrical Rough-In | 11/8/2005 | 11/9/2005 | 11/9/2005 9:37:11 AM | A | PART |
|
|
bonding on new swimming pool and wiring for pool pump. Internet Inspection Request from: Andy Rose ok e grid ok also
|
ELE05-04051
| Temporary Service | 11/8/2005 | 11/9/2005 | 11/9/2005 9:11:21 AM | A | FAIL |
|
|
HZ; Phone #: ###-#### Internet Inspection Request from: Barbara Moore cor. called 250.24 shall make connection between grd and neutral
|
ELE05-02596
| Final | 11/8/2005 | 11/9/2005 | 11/9/2005 8:41:52 AM | A | FAIL |
|
|
warren; Phone #: ###-#### Internet Inspection Request from: Letitia Mesa 110.3 shall not use cable ties to secure flex, 300.10 & 314.3 shall install bonding means or use non metallic raceways where non metallic enclosures encountered met contractor at site
|
ELE05-04038
| Rough-In Permanent Service | 11/7/2005 | 11/9/2005 | 11/8/2005 7:42:25 PM | P | CANC |
|
|
Rough in for underground conduit only. ; Phone #: ###-#### Internet Inspection Request from: Randy Fletcher Inspection cancelled from web by: Randy Fletcher
|
ELE05-04057
| Final | 11/8/2005 | 11/9/2005 | 11/8/2005 2:20:35 PM | A | CANC |
|
|
Phone #: ###-#### Internet Inspection Request from: Dana Moyer Inspection cancelled from web by: Dana Moyer
|