Inspections for the day of: Wednesday, November 9, 2005.
Number of inspections: 9
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR05-00647 INSP-Sprinkler Rough-in/Hydro11/8/200511/9/200511/9/2005 5:09:48 PMAPART
Overhead rough-in is satisfactory, AG and UG hydrostatic tests also passed inspection, will final when alarms are connected and forward flow is performed.
BLD05-01733 FIRE-Final Inspection11/9/200511/9/200511/9/2005 3:51:39 PMPFAIL
Project will require fire sprinkler modifications as the newly installed duct is over 4' and significantly blocks coverage of the sprinklers from above, a fire sprinkler permit will be needed to perform this work.
FIR05-00413 INSP-Final Inspection11/8/200511/9/200511/9/2005 3:34:41 PMPPASS
Fire alarm passed inspection.
FIR05-00372 INSP-Final Inspection11/9/200511/9/200511/9/2005 1:40:54 PMPFAIL
An additional 11 item correcton notice was given to the subcontractor, inspection stopped at this point due to the excessive number of defficiencies. Mezzanine not inspected for final yet, contractor to walk project again and call for re-inspection when project is code compliant. Re-inspection fees apply.
FIR05-00076 INSP-Alarm Testing11/9/200511/9/200511/9/2005 1:17:49 PMPPART
The north elevator remains to be completed and tested, final pending verification of resubmittals for field changes.
FIR05-00499 INSP-Final Inspection11/9/200511/9/200511/9/2005 1:14:28 PMPPART
UG fire supply line is acceptable to cover pending verification and approval of field modifications from original approved plans via resubmittals.
FIR05-00039 INSP-Final Inspection11/8/200511/9/200511/9/2005 9:32:34 AMAPASS
UG fire supply line permit finaled.
FIR05-00585 INSP-Final Inspection11/7/200511/9/200511/9/2005 9:22:19 AMAPASS
Fire alarm finaled.
FIR05-00580 INSP-Final Inspection11/7/200511/9/200511/9/2005 9:21:42 AMAPASS
Fire alarm passed inspection.