FIR07-00415
| FIR-Aging Inspection | 11/9/2007 | 11/9/2007 | 11/14/2007 9:28:20 AM | | DEFR |
|
|
Work in progress.
|
FIR07-00905
| INSP-Sprinkler Rough-in/Hydro | 11/9/2007 | 11/9/2007 | 11/11/2007 9:42:24 PM | P | FAIL |
|
|
Ok to cover under ground from the north west corner of the existing building to the future building. NOT OK TO COVER FROM NORTH WEST CORNER OF EXISTING BUILDING TO WATER MAIN, LESS THAN 4' 6" DEEP REQUIRED CODE IS 4' 6".MANY AREAS WERE 3" to 6" TO SHALLOW. DO NOT COVER UNTIL FIELD INSPECTED.
|
FIR07-00700
| INSP-Final Inspection | 11/9/2007 | 11/9/2007 | 11/9/2007 3:22:56 PM | A | PASS |
|
|
Complete foward flush,Test flow switch tamper switch and bell.Test connection to alarm panel.KR
|
FIR07-00205
| INSP-Final Inspection | 11/8/2007 | 11/9/2007 | 11/9/2007 2:41:40 PM | A | CANC |
|
|
Mike B is the contact, thank you. Phone #: ###-#### Internet Inspection Request from: Stan Beus
|
FIR07-00837
| INSP-Final Inspection | 11/6/2007 | 11/9/2007 | 11/9/2007 2:36:38 PM | P | FAIL |
|
|
No approved set of plans on site.Double doors #515 storage did not close all the way when released when fire alarm was activated. All other devices function properly.KR
|
FIR07-00786
| INSP-Final Inspection | 11/8/2007 | 11/9/2007 | 11/9/2007 11:44:40 AM | A | PASS |
|
|
Test fire alarm per approved plans.
|
FIR07-00156
| INSP-Final Inspection | 11/8/2007 | 11/9/2007 | 11/9/2007 10:01:19 AM | A | PASS |
|
|
Picked up copy of state elevator permit for final and NFPA record of completion.
|