FIR10-00221
| FIR-Aging Inspection | 11/9/2010 | 11/9/2010 | 11/17/2010 4:55:43 PM | | FAIL |
|
|
Need site inspection request for final.
|
FIR09-00270
| INSP-Final Inspection | 11/8/2010 | 11/9/2010 | 11/11/2010 4:58:38 PM | A | PASS |
|
|
Fire alarm work passed inspection, permit finaled.
|
FIR10-00169
| FIR-Aging Inspection | 11/9/2010 | 11/9/2010 | 11/9/2010 5:57:10 PM | | NR |
|
|
In progress
|
FIR10-00180
| FIR-Aging Inspection | 11/9/2010 | 11/9/2010 | 11/9/2010 5:54:27 PM | | FAIL |
|
|
See activity notes 4/26.
|
BLD10-01139
| FIRE-Final Inspection | 11/9/2010 | 11/9/2010 | 11/9/2010 5:43:07 PM | P | FAIL |
|
|
Post max occupant load sign, repair one exit sign/EM light, provide test for the two new duct detectors, fire extinguishers are overdue certification.
|
FIR10-00477
| INSP-Sprinkler Rough-in/Hydro | 11/8/2010 | 11/9/2010 | 11/9/2010 5:34:16 PM | P | PART |
|
|
New branchline install okayed, new drops incomplete at this time.
|
FIR10-00449
| INSP-Sprinkler Rough-in/Hydro | 11/8/2010 | 11/9/2010 | 11/9/2010 5:31:11 PM | P | NR |
|
|
Project not in condition for a rough-in inspection at this time. Ceiling grid and new pendent heads are not yet installed at several areas.
|
FIR10-00538
| INSP-Final Inspection | 11/8/2010 | 11/9/2010 | 11/9/2010 5:21:37 PM | P | FAIL |
|
|
Pendent heads at some locations are obstructed by close proximity to adjacent ductwork affecting pattern development.
|
FIR10-00539
| INSP-Final Inspection | 11/8/2010 | 11/9/2010 | 11/9/2010 5:05:37 PM | P | PASS |
|
|
Fire sprinkler work passed inspection, both rough-in and final approved.
|
FIR10-00163
| INSP-Final Inspection | 11/8/2010 | 11/9/2010 | 11/9/2010 4:57:39 PM | A | FAIL |
|
|
Panel failed to report supervisory conditions offsite.
|
FIR10-00164
| INSP-Final Inspection | 11/8/2010 | 11/9/2010 | 11/9/2010 4:51:05 PM | A | FAIL |
|
|
Account information at central station needs revised to match signals sent. All points reported as "3rd floor RTU".
|
FIR10-00170
| INSP-Final Inspection | 11/8/2010 | 11/9/2010 | 11/9/2010 12:39:33 PM | A | FAIL |
|
|
Signals were not recieved at offsite monitoring.
|
FIR10-00526
| INSP-Final Inspection | 11/4/2010 | 11/9/2010 | 11/9/2010 12:38:08 PM | A | PASS |
|
|
Scope of fire sprinkler permit work completed. Inspection passed.
|