Inspections for the day of: Tuesday, November 9, 2010.
Number of inspections: 13
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR10-00221 FIR-Aging Inspection11/9/201011/9/201011/17/2010 4:55:43 PM FAIL
Need site inspection request for final.
FIR09-00270 INSP-Final Inspection11/8/201011/9/201011/11/2010 4:58:38 PMAPASS
Fire alarm work passed inspection, permit finaled.
FIR10-00169 FIR-Aging Inspection11/9/201011/9/201011/9/2010 5:57:10 PM NR
In progress
FIR10-00180 FIR-Aging Inspection11/9/201011/9/201011/9/2010 5:54:27 PM FAIL
See activity notes 4/26.
BLD10-01139 FIRE-Final Inspection11/9/201011/9/201011/9/2010 5:43:07 PMPFAIL
Post max occupant load sign, repair one exit sign/EM light, provide test for the two new duct detectors, fire extinguishers are overdue certification.
FIR10-00477 INSP-Sprinkler Rough-in/Hydro11/8/201011/9/201011/9/2010 5:34:16 PMPPART
New branchline install okayed, new drops incomplete at this time.
FIR10-00449 INSP-Sprinkler Rough-in/Hydro11/8/201011/9/201011/9/2010 5:31:11 PMPNR
Project not in condition for a rough-in inspection at this time. Ceiling grid and new pendent heads are not yet installed at several areas.
FIR10-00538 INSP-Final Inspection11/8/201011/9/201011/9/2010 5:21:37 PMPFAIL
Pendent heads at some locations are obstructed by close proximity to adjacent ductwork affecting pattern development.
FIR10-00539 INSP-Final Inspection11/8/201011/9/201011/9/2010 5:05:37 PMPPASS
Fire sprinkler work passed inspection, both rough-in and final approved.
FIR10-00163 INSP-Final Inspection11/8/201011/9/201011/9/2010 4:57:39 PMAFAIL
Panel failed to report supervisory conditions offsite.
FIR10-00164 INSP-Final Inspection11/8/201011/9/201011/9/2010 4:51:05 PMAFAIL
Account information at central station needs revised to match signals sent. All points reported as "3rd floor RTU".
FIR10-00170 INSP-Final Inspection11/8/201011/9/201011/9/2010 12:39:33 PMAFAIL
Signals were not recieved at offsite monitoring.
FIR10-00526 INSP-Final Inspection11/4/201011/9/201011/9/2010 12:38:08 PMAPASS
Scope of fire sprinkler permit work completed. Inspection passed.