Inspections for the day of: Monday, November 9, 2015.
Number of inspections: 12
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRex Boyles
TitleELE-INSPECTOR
Phone #685-9023
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE12-02164 ELE-Aging Inspection11/9/201511/9/201511/10/2015 12:02:10 PM DONE
John is still looking into it
ELE15-03100 Final11/6/201511/9/201511/9/2015 3:16:57 PMPNR
Phone #: ###-#### Inspection requested via web by Celinda Winters not ready, floor plug trim, reception area trim, arc flash warning labels, dead front on rooftop panel
ELE15-03100 Electrical Rough-In11/9/201511/9/201511/9/2015 3:05:06 PMPPASS
Phone #: ###-#### Inspection requested via web by Celinda Winters r/i cabinet electrical at reception desk ok
ELE15-01928 Electrical Rough-In11/9/201511/9/201511/9/2015 2:14:00 PMPPASS
Partial ceiling please. Phone #: ###-#### Inspection requested via web by Scott Campbell (john) r/i ceiling in play area and borders ok in other areas (verify areas with electrician first)
ELE15-01473 Electrical Rough-In11/9/201511/9/201511/9/2015 1:42:33 PMPPASS
Treaon Phone #: ###-#### r/i soffit/ hard lid at front entry ok
ELE15-02822 Final11/9/201511/9/201511/9/2015 1:22:10 PMPFAIL
Pedestal meter Phone #: ###-#### Inspection requested via web by Jim Williams 110.24(A)-Service equipment in other than dwelling units shall be legibly marked in the field with the maximum available fault current. 110.16 electrical equipment in other than dwellings shall be marked with arc flash warning label. Please put new address for new tenant (ST. Lukes) Please call for "perm. service" when ready
ELE15-03319 Electrical Rough-In11/9/201511/9/201511/9/2015 12:39:34 PMPPASS
Mike McCarrol is on site. Phone #: ###-#### Inspection requested via web by Brian Caruso r/i wall with loadcenters ok to cover
ELE15-02460 Electrical Rough-In11/6/201511/9/201511/9/2015 10:08:22 AMAPASS
partial ceiling Inspection, contact is Greg Milburn at ###-####. thank you. Phone #: ###-#### Inspection requested via web by Debby Pierce r/i outer perimeter offices on 2nd floor ok to cover
ELE15-03245 Permanent Service11/6/201511/9/201511/9/2015 9:49:10 AMAPASS
Treon Phone #: ###-#### p/s o/h rec ok
ELE15-03621 Electrical Rough-In11/6/201511/9/201511/9/2015 9:27:32 AMAPASS
Lock box code is 1021, if you have any questions, please call Jake ###-####, Thank You. Phone #: ###-#### Inspection requested via web by Clay Morgan r/i ok change out devices and install ground rod
ELE15-03621 Final11/9/201511/9/201511/9/2015 9:26:43 AMPPASS
Lock box code is 1021, if you have any questions, please call Jake ###-####, Thank You. Phone #: ###-#### Inspection requested via web by Clay Morgan final ok
GCE15-00094 GCE-Final11/6/201511/9/201511/9/2015 8:18:29 AMAPASS
Brandon ###-#### garage code: ASIN or lockbox: 234 Please call Gary Asin if no access - ###-#### final ok