ELE15-02641
| Final | 11/9/2016 | 11/9/2016 | 11/9/2016 4:05:02 PM | P | FAIL |
|
|
Please call 30 minutes prior Phone #: ###-#### Inspection requested via web by Kerri Hamilton 601 ok, 602 ok, 603 ok seal around patio receptacle. 604 210.52- Receptacle outlet shall be located with in 6' of bed closet door. Switch cover off for patch. 605 210.52- Receptacle outlet shall be located with in 6' of master bed door. 406.12- 2 patio outdoor receptacles shall be tamper resistant. 300.15- Switch covers off for patch. Parking ramp door start stop station conduit subject to weather shall have raintight fittings. Notes: All Floor heat circuits for future floor heat permit will be required. All other areas checked out ok in all floors.
|
ELE14-03316
| Final | 11/9/2016 | 11/9/2016 | 11/9/2016 2:55:00 PM | P | PART |
|
|
Warren Wing with State of Idaho has been notified of concerns with elevator rooms. Temp occupancy of garage expansion ok
|
ELE16-01838
| Final | 11/9/2016 | 11/9/2016 | 11/9/2016 2:53:03 PM | P | PART |
|
|
SWHQ Level 8 Power TI and Lighting TI Phone #: ###-#### Inspection requested via web by Tom Betty Area noted temp occupancy
|
ELE16-00089
| Final | 11/9/2016 | 11/9/2016 | 11/9/2016 1:35:44 PM | P | PASS |
|
|
Inspect lighting in delivery area. Phone #: ###-#### Inspection requested via web by Rafael Castillo Correction complete, signed pages of level 5 temp office for GBAD permit. Final ok
|
ELE16-01652
| Conference | 11/8/2016 | 11/9/2016 | 11/9/2016 1:34:36 PM | P | DONE |
|
|
Rock they are trying to get an ok to occupy the restrooms. Not sure what we need to do to make this happen Phone #: ###-#### Inspection requested via web by John Rourke Discussed area to have temp occupancy. Only area of building not ready is information office.
|
ELE16-01652
| Final | 11/9/2016 | 11/9/2016 | 11/9/2016 1:34:17 PM | P | PART |
|
|
Rock they are trying to get an ok to occupy the restrooms. Not sure what we need to do to make this happen Phone #: ###-#### Inspection requested via web by John Rourke Information office not included. Rest of building and center area of grove ok to occupy. GFCI protection in place and 1 pole light to mount after christmas tree is set.
|
ELE16-01946
| Electrical Rough-In | 11/9/2016 | 11/9/2016 | 11/9/2016 11:21:55 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Kerri Hamilton Discussed required grounding electrode system and conductor needed. 3000 amp service with multiple sets of service entrance conductors exceeding 1100 kcmil copper or 1750 aluminum so 3/0 needed. A single undergound water pipe shall be supplemented by additional pipe or rod. 2 underground water pipe systems present. No other grounding electrodes described in 250.52 present. 1st floor wall rough in as noted on contractor print rough in ok cover
|
ELE16-02937
| Final | 11/8/2016 | 11/9/2016 | 11/9/2016 10:21:46 AM | A | PASS |
|
|
For access please call Joe 1/2 hr prior to inspection. ###-#### Phone #: ###-#### Inspection requested via web by Terry Scott Final ok
|
ELE16-02985
| Final | 11/8/2016 | 11/9/2016 | 11/9/2016 10:06:29 AM | A | FAIL |
|
|
Please call ###-#### - Jake 30 min in advance so someone can meet inspector. Thanks, Dustin Phone #: ###-#### Inspection requested via web by Dustin Kuester 210.52(D)- Receptacles that serve bathroom vanities shall be located on wall oer partition adjacent to basin. Receptacles located in cabinets can remain. Spoke with contact and left correction notice.
|
ELE16-02959
| Final | 11/8/2016 | 11/9/2016 | 11/9/2016 9:40:52 AM | A | FAIL |
|
|
Phone #: ###-#### Inspection requested via web by Alan Lusk 210.8- All receptacle outlets located in kitchen area that serve counter top areas shall have GFCI protection. Front outdoor receptacle as well. 314.21- Drywall shall be repaired where open around boxes more than 1/8". Dryer, 2 up bed, 1 low in kitchen area. 406.6- Washer receptacle missing cover plate. 408.4 Circuit directory shall be complete. Trim back soffit receptacle.
|
ELE16-00795
| Electrical Rough-In | 11/8/2016 | 11/9/2016 | 11/9/2016 8:45:07 AM | A | PASS |
|
|
bonding of stem walls at pool area Phone #: ###-#### Inspection requested via web by Kevin Koomler #8 stub to inside of pool bar area, needs to tie to perimeter bond. Stem wall bond rough in ok cover
|