Inspections for the day of: Wednesday, November 9, 2016.
Number of inspections: 7
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorKatie Marron
TitleFIRE INSPECTOR
Phone #395-7809
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR16-00088 INSP-Sprinkler Rough-in11/8/201611/9/201611/9/2016 4:33:25 PMPPASS
Rough to cover on 6th floor. Dwelling units Ok to cover except connections to riser and trash shute loop.

Dry pendants were in but need to be adjusted so that deflectors are level.

From last inspection, Rm 302 requires additional sprinkler at upper ceiling. This was corrected ahead of time for the corrresponding room on the 6th floor.
FIR16-00569 INSP-Sprinkler Rough-in11/9/201611/9/201611/9/2016 3:32:23 PMPCANC
Will be rescheduled for tomorrow. Arrived on site but contractor had left already for the day. Adam Phone #: ###-####
FIR16-00534 INSP-Sprinkler Rough-in11/9/201611/9/201611/9/2016 3:04:56 PMPPASS
Completed rough-in of grid ceiling. Ok to cover.
FIR16-00695 INSP-Sprinkler Rough-in11/9/201611/9/201611/9/2016 2:32:12 PMPPASS
Rough-in completed. Ok to cover.
NAF16-00055 INSP-Supply line flush11/8/201611/9/201611/9/2016 1:34:15 PMPDONE
Supply line flush completed satisfactory.
FIR16-00585 INSP-Final Inspection11/9/201611/9/201611/9/2016 11:09:31 AMPPASS
Scope of work complete. Permit Finaled.
FIR16-00681 INSP-Final Inspection11/8/201611/9/201611/9/2016 11:08:31 AMPPASS
Verified new bell is functional and old bells removed. Scope of work complete. Permit Finaled